beautypg.com

VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 24

background image

24

4 Mounting

VEGAPULS 61 • Profibus PA

36501-EN-121011

0 %

100 %

1
2

5

4

3

6

Fig. 21: Configuration bypass
1 Radar sensor

2 Marking of the polarisation direction

3 Instrument flange

4 Distance sensor reference plane to upper tube connection

5 Distance of the tube connections

6 Ball valve with complete opening

Instructions for orientation:

Note marking of the polarisation plane on the sensor

With threaded fitting, the marking is on the hexagon, with flange

connection between the two flange holes

The pipe connections to the vessel must be in one plane with this

marking

Instructions for the measurement:

The 100 % point must not be above the upper tube connection to

the vessel

The 0 % point must not be below the lower tube connection to the

vessel

Min. distance sensor reference plane to the upper edge upper

tube connection > 300 mm

The tube diameter must be at least DN 40 or 1½" with antenna

size 40 mm (1½")

For the parameter adjustment, select "Application standpipe" and

enter the tube diameter to compensate errors due to running time

shift

A false signal suppression with integrated sensor is recommended

but not mandatory