8 Maintenance and fault rectification
VEGABAR 66 • Profibus PA
36739-EN-130321
Connect the signal conditioning instrument to power supply and
provide the connection from the PC to the instrument via the interface
adapter. Start PACTware and go via the menu "Project" to the VEGA
project assistant. Select "USB" and "Set instruments online". Activate
the project assistant with "Start". The assistant establishes the con-
nection automatically and opens the parameter adjustment window
"Sensor # online parameter adjustment". Connect this parameter
adjustment window before you carry out further steps.
Select with the right mouse key the sensor in the project and go to
"Additional function". Then click to "Software update". The window
"Sensor # software update" opens. PACTware checks now the sensor
data and displays the actual hardware and software version of the
sensor. This takes approximately 60 s.
Push the button "Update software" and select the previously extracted
hex file. Then the software update can be started. The additional files
are installed automatically. Depending on the sensor, this procedure
lasts up to 1 h. Then the message appears ""Software update suc-
cessfully executed".
8.6 Instrument repair
If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage
www.vega.com under: "Downloads - Forms and certificates - Repair
form".
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
•
Print and fill out one form per instrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please ask the agency serving you for the address of your return
shipment. You can find the respective contact data on our website
www.vega.com under: "Company - VEGA worldwide"
Prepare update
Load software into sen-
sor