22

5 Connecting to power supply

VEGABAR 66 • Profibus PA

36739-EN-130321

Fig. 12: Connection steps 6 and 7

Proceed as follows:
1. Loosen the four screws on the housing base with an Allen key

size 4

2. Remove the mounting plate from the housing socket

3

2

1

Fig. 13: Components of the external housing
1 Screws

2 Wall mounting plate

3 Cable gland

3. Loop the connection cable through the cable entry on the housing

base

2)

IP 68 version with exter-

nal housing

2)

The connection cable is already preconfectioned. If necessary, shorten it

to the requested length, cut the breather capillaries clean. Remove approx.

5 cm of the cable mantle, strip approx. 1 cm insulation from the ends of the

individual wires. After shortening the cable, fasten the type plate with support

back onto the cable.