VEGA VEGABAR 66 Profibus PA User Manual
Page 36
36
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 66 • Profibus PA
36739-EN-130321
Information:
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Edit the % value in the menu item "Max. adjustment" with [OK].
Max. adjustment
+100.0 %
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal meas-
uring range of the sensor (in the above example 1 bar = 1000 mbar).
2. Set the requested percentage value with [->] and [OK].
3. Confirm with [OK] and edit the requested mbar value.
4. Set the requested mbar value with [+] and [->].
5. Confirm with [OK] and move to the menu overview with [ESC].
The max. adjustment is finished.
Information:
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Process pressure measurement
Set up VEGABAR 66 in the following sequence:
1. Select application "Process pressure measurement"
2. Select the unit of measurement
3. Carry out a position correction
4. Carrying out zero adjustment
5. Carry out span adjustment
In the menu item "Adjustment unit" you select the physical unit in
which the adjustment should be carried out, e.g. mbar, bar, psi…
The position correction compensates the influence of the mounting
position or static pressure on the measurement. It does not influence
the adjustment values.
In the menu items "zero" and "span" you determine the span of the
sensor, the span corresponds to the end value.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specifications!
Carry out max. adjust-
ment
Parameter adjustment
"Process pressure meas-
urement"