8 Maintenance and fault rectification

PLICSRADIO R62 • Wireless receiving unit (multiple channel)

32970-EN-130228

8 Maintenance and fault rectification

8.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

8.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

A maximum of reliability is ensured. Nevertheless, faults can occur

during operation. These may be caused by the following, e.g.:

Measured value from sensor not correct

Voltage supply

Interference on the cables

The first measures to be taken are to check the input and output

signal as well as to evaluate the error messages via the display. The

procedure is described below. Further comprehensive diagnostics

can be carried out on a PC with PACTware and the suitable DTM. In

many cases, the causes can be determined in this way and faults

rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error code Cause

Rectification

No indication

of the signal

strength

Wrong adjustment

of the radio channel,

address of the ra-

dio PIN

– Set the transmitter and receiver to

the same radio channel/address/

radio PIN

E034

EEPROM CRC error

– Switch the instrument off and on

– Carry out a reset

– Send instrument for repair

E035

ROM CRC error

– Switch the instrument off and on

– Carry out a reset

– Send instrument for repair

E036

Instrument software

not executable (dur-

ing software update

or after failed update)

– Wait until software update is finished

– Carry out another software update

E042

Hardware error with

selfcheck

– Send instrument for repair

Reaction when malfunc-

tions occur

Failure reasons

Fault rectification

24 hour service hotline

Error messages via the

display and adjustment

module