4 software update – VEGA VEGAFLEX 67 (-200…+400°C) 4 … 20 mA_HART two-wire User Manual

Page 42

background image

l

A

t the factory by VEGA

l

O

r on site by the user

I

n both cases, the sensor serial number is necessary. The serial

numbers are stated on the type label of the instrument, inside the
housing or on the delivery note.

Information:
W

hen loading on site, first of all the order data must be downloaded

from the Internet (see operating instructions manual "Electronics
module
").

T

he electronics modules are adapted to the respective sensor and

distinguish also in the signal output or power supply.

E

lectronics module FX-E.67H suitable for VEGAFLEX 67 - 4 … 20 mA/

HART:

l

FX-E.

67HX (X =

without approvals)

l

FX-E.

67HC (C =

approvals XM, CX, CM, CK, CI, DX, DM, DI

according to product list)

8

.4 Software update

T

he software version of VEGAFLEX 67 can be determined as follows:

l

on the type label of the electronics

l

via the indicating and adjustment module

l

via PACTware

Y

ou can view all software histories on our website www.vega.com.

M

ake use of this advantage and get registered for update information

via e-mail.

T

he following components are required to update the sensor software:

l

S

ensor

l

V

oltage supply

l

VEGACONNECT

l

PC

with PACTware

l

C

urrent sensor software as file

A

t "www.vega.com/downloads" go to "Software". Select under "plics

sensors and instruments", "Firmware updates" the respective instru-
ment series and software version. Load the zip file via the right mouse
key with "Save target as" e.g. on the desktop of your PC. Move with the
right mouse key to the folder and select "Extract all". Save the
extracted files, for example on the desktop.

C

onnect the signal conditioning instrument to power supply and

provide the connection from the PC to the instrument via the interface
adapter. Start PACTware and go via the menu "Project" to the VEGA
project assistant
. Select "USB" and "Set instruments online". Activate

Assignment

4

… 20 mA/HART

Load sensor software to
PC

Prepare update

42

VEGAFLEX

67 • 4 … 20

mA/HART - two-wire

8 M

aintenance and fault rectification

32311

-EN

-120329