2 parameter adjustment with pactware – VEGA VEGAFLEX 67 (-200…+400°C) 4 … 20 mA_HART two-wire User Manual
Page 38
N
ecessary components:
l
VEGAFLEX
67
l
PC
with PACTware and suitable VEGA DTM
l
VEGACONNECT
l
P
ower supply unit or processing system
1
2
4
3
OPEN
TWIST
USB
LO
CK
Fig. 21: Connecting the PC via HART to the signal cable
1
VEGAFLEX 67
2
HART resistance 250 Ω (optional depending on processing)
3
Connection cable with 2 mm pins and terminals
4
Processing system/PLC/Voltage supply
N
ecessary components:
l
VEGAFLEX
67
l
PC
with PACTware and suitable VEGA DTM
l
VEGACONNECT
l
HART
resistance approx. 250 Ω
l
P
ower supply unit or processing system
Note:
W
ith power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e. g. to the VEGA instruments VEGATRENN
149A, VEGADIS 371, VEGAMET 381. C
ommon Ex separators are
also usually equipped with a sufficient current limitation resistance. In
such cases, VEGACONNECT 4 can be connected parallel to the
4 … 20
mA cable.
7
.2 Parameter adjustment with PACTware
F
urther setup steps are described in the operating instructions manual
"DTM C
ollection/PACTware" attached to each CD and which can also
be downloaded from our homepage. A detailed description is available
in the online help of PACTware and the VEGA DTMs.
Note:
K
eep in mind that for setup of VEGAFLEX 67, DTM-Collection in the
actual version must be used.
VEGACONNECT via
HART
38
VEGAFLEX
67 • 4 … 20
mA/HART - two-wire
7 S
et up with PACTware and other adjustment programs
32311
-EN
-120329