beautypg.com

VEGA VEGASWING 61 - two-wire User Manual

Page 22

background image

22

6 Setup

VEGASWING 61 • - two-wire

29227-EN-130409

Sensor

current -

Sensor

Level relay

A - overfill

protection

Signal lamp

A - Overfill

protection

Level relay

B - dry run

protection

Signal lamp

B - Dry run

protection

Fail safe

relay

Control

lamp

1. Fault sig-

nal
approx. 0.6 s
+ t

A

2)

< 1.8 mA

currentless

currentless

currentless

2. Empty

signal
(approx.

1.5 s)

approx.

8 mA

energized

currentless

energized

3. Full signal
(approx.

1.5 s)

approx.

16 mA

currentless

energized

energized

4. Return

to current

operating

condition

Note:

When used as overfill protection according to WHG and use in meas-

uring chains according IEC 61508, mode B is not permitted.

Test passed

Interference signal (< 3.6 mA) ≥ 400 ms

Uncovered (approx. 8 mA) ≥ 1 s

Covered (approx. 16 mA) ≥ 1 s

Test not passed

Interference signal (< 3.6 mA) < 400 ms / ≥ 750 ms

Uncovered (approx. 8 mA) < 1 s / ≥ 2 s

Covered (approx. 16 mA) < 1 s / ≥ 2 s

Test assessment (SPLC)

2)

Starting time of the voltage supply