6 Setup

VEGASWING 61 • - two-wire

29227-EN-130409

If you are using a signal conditioning instrument of type VEGATOR for

this purpose, you can carry out the test with the integrated test key.

The test key is recessed in the front plate of the signal conditioning

insturment. Push the test key for > 2 seconds with a suitable object

(screwdriver, pen, etc.).
When the VEGASWING 61 is connected to a processing system or

an SPLC, you have to interrupt the connection cable to the sensor for

> 2 seconds. The switching delay must be set to 0.5 s.
After releasing the test key or interrupting the connection cable to the

sensor, the complete measuring system can be checked on correct

function. The following operating conditions are simulated during the

test:

Fault message

Empty signal

Full signal

1

2

3

16

I/mA

8

1,8

0,6

1,5

1,5

t/s

Fig. 27: Flow chart of the function test
1 Full signal

2 Empty signal

3 Fault message

Check if all three switching conditions occur in the correct sequence

and the stated time period. If this is not the case, there is a fault in the

measuring system (see also the operating instructions manual of the

signal conditioning instrument). Keep in mind that connected instru-

ments are activated during the function test. By doing this, you can

check the correct function of the measuring system.
Note:

Keep in mind that the starting time t

A

of the voltage supply can extend

the time up to the first switching (e.g. VEGATOR 636: +1 s)

After releasing the button or after a brief line break.
The specified times apply with a tolerance of ±20 %.

Test procedure