5 Connecting to power supply

VEGASWING 61 • - two-wire

29227-EN-130409

8. Check the hold of the wires in the terminals by lightly pulling on

them

9. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

10. Screw the housing cover back on
The electrical connection is hence finished.

5.3 Wiring plan, single chamber housing

The following illustrations apply to the non-Ex as well as to the Ex-d

version.

1

4

4

4

2

3

Fig. 8: Material versions, single chamber housing
1 Plastic (not with EEx d)

2 Aluminium

3 Stainless steel (not with EEx d)

4 Filter element for pressure compensation or blind plug with version IP 66/

IP 68, 1 bar (not with EEx d)

Z

+

0,5 g / cm3

0,7 g / cm3

11-36V DC

4

5

1

2

3

1

2

Fig. 9: Electronics and connection compartment
1 Control lamp

2 DIL switch for sensitivity adjustment

3 Ground terminal

4 Connection terminals

5 Processing system or PLC

We recommend connecting VEGASWING 61 in such a way that the

switching circuit is open when there is a level signal, line break or

failure (safe condition).
For connection to a VEGATOR signal conditioning instrument dto.

Ex, WHG. The sensor is powered by the connected VEGATOR signal

conditioning instrument. Further information is available in chapter

Housing overview

Electronics and connec-

tion compartment

Wiring plan