VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 61
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug
9)
-
Single chamber housing
l
1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5
or:
l
1 x closing cap M20 x 1.5; 1 x blind stopper
M
20 x 1.5
or:
l
1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
l
1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5
-
Double chamber housing
l
1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5; 1 x blind stopper
M
16 x 1.5 or optionally available with 1 x plug
M
12 x 1 for VEGADIS 61
or:
l
1 x closing cap ½ NPT, 1 x blind stopper
½ NPT
, 1 x blind stopper M16 x 1.5 or
optionally 1 x plug M12 x 1 for VEGADIS 61
or:
l
1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; 1 x blind stopper M16 x 1.5
or optionally available with 1 x plug M12 x 1 for
VEGADIS
61
Spring-loaded terminals for wire cross-sec-
tion
> 2
.5 mm² (AWG 14)
Electromechanical data - version IP 66/IP 68 (1 bar)
Cable entry
-
Single chamber housing
1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M
20 x 1.5
-
Double chamber housing
1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M
20 x 1.5; 1 x blind stopper M16 x 1.5
Connection cable
-
Wire cross-section
0.5 mm² (AWG 20)
-
Wire resistance
< 0
.036 Ω/m
-
Tensile strength
< 1200 N
(270 lbf)
-
Standard length
5 m (16.4 ft)
-
Max. length
1000 m (3280 ft)
-
Min. bending radius
25 mm (0.984 in) with 25 °C (77 °F)
9)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/
8" FF.
VEGAPULS
62 • Foundation Fieldbus
61
10 Supplement
28450
-
EN
-090305