> 300 mm

Fig. 16: VEGAPULS 62 in a bypass tube. The polarisation marking on the
process fitting must be in one plane with the tube holes or the tube connection
openings.

1

Marking of the polarisation direction

When the sensor is mounted on a bypass tube, the distance from
VEGAPULS

62 to the upper tube connection should be approx.

300 mm (11.81 in) or more. In case of extremely rough tube inner
walls, you should use an inserted tube (tube in tube) or a radar sensor
with tube antenna.

Information:
With VEGAPULS 62 in flange version, the polarisation plane is always
in the center between two flange holes.