6.4 Setup procedure

As VEGAPULS 62 is a distance measuring instrument, the distance
from the sensor to the product surface is measured. To have the real
product level displayed, an allocation of the measured distance to the
percentage height must be made. To carry out this adjustment, the
distance is entered with full and empty vessel. If these values are not
known, an adjustment with the distance values, e.g. 10 % and 90 % is
also possible. Starting point for these distance specifications is always
the seal surface of the thread or flange. With these settings, the real
level is calculated. Furthermore the operating range of the sensor is
limited from maximum to the required range.

The real product level during this adjustment is not important, because
the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.

Caution:
If there is a separation of liquids with different dielectric values in the
vessel, e.g. from condensation, VEGAPULS 62 can detect under
certain circumstances only the medium with the higher dielectric value.

Keep in mind that interfaces can cause faulty measurements.

If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially
designed for interface measurement.

In the main menu item "Basic adjustment", the individual submenu
items should be selected one after the other and provided with the
correct parameter values.

Start your parameter adjustment with the following menu items of the
basic adjustment:

Proceed as follows:

1

Move from the measured value display to the main menu by
pushing [OK].

Basic adjustment

Display
Diagnostics
Service
Info

2

Select the menu item "Basic adjustment" with [->] and confirm with
[OK]

. Now the menu item "Min. adjustment" is displayed.

Min. adjustment

0.00 %

=

5.000 m(d)

4.000 m(d)

Parameter adjustment

Carrying out min. ad-
justment

VEGAPULS

62 • Foundation Fieldbus

39