5 diagnosis, 1 simulation, 2 error removal – VEGA VEGAFLEX 52V User Manual
Page 32
32
VEGAFLEX 51V and 52V
5 Diagnosis
5.1 Simulation
For simulation of a certain filling, you can
enquire the function "Simulation" on the ad-
justment module MINICOM, in the software
program VVO or in the signal conditioning
instrument VEGAMET (V).
You simulate a certain measured value. Note
that connected instruments such as e.g. a
DCS react according to their adjustments
and probably activate alarm signals or sys-
tem functions.
5.2 Error removal
Error
Error removal
E 013
Sensor does not find
- Message is displayed during feeding
level echo
phase.
- When the message remains, the DK-value
of the medium can be too low.
Check the useful and noise level.
See 4.2 Adjustment with adjustment module
MINICOM / 6. Useful and noise level.
When the message still remains, carry out
a new adjustment.
E 017
Adjustment span too small
Carry out a new adjustment.
Note that the difference between min. and
max.-adjustment is at least 10 mm.
E 036
Software-Update incorrect
Return the instrument for repair.
E 040
Hardware failure /
Check all connection lines.
electronics defect
Contact our service department.
Diagnosis