Adjustment steps, Adjustment – VEGA VEGAFLEX 52V User Manual

Page 24

background image

24

VEGAFLEX 51V and 52V

Set-up / Adjustment module MINICOM

Adjustment steps

On the following pages you see the menu
plan of the adjustment module MINICOM.

Set-up the sensor in the following sequence.
The numbers correspond to the sequence of
a set-up. The numbers are stated near the
appropriate menu points in the menu plan on
the following pages.

1. Adjustment
2. Conditioning
3. Outputs
4. Operating range
5. Meas. conditions
6. Indication of the useful and noise level

1. Adjustment

Under the menu point "

Adjustment“ you in-

form the sensor with which span it should
work.

You can carry out the adjustment without or
with medium. Generally you will carry out the
adjustment without medium as you can adjust
without vessel filling.

Max.

Min.

100 % (distance to the medium
0,300 m) correspond to
1200 l, e.g. 20 mA

Span

0 % (distance to the medium
5,850 m) correspond to
456 l, e.g. 4 mA)

Ad-
just-
ment

Para-
meter
adjust-
ment

Sensor

m(d)

4.700

without
medium

Ad-
just-
ment
in

m(d)

0.0 %

at

m (d)

XX.XXX

(Min-adjustment)

OK

OK

OK

OK

Adjustment without medium

Enter with the "

+“ and "–“ key the dis-

tance to the medium your sensor has at
0 % filling (example: 5,850 m)
If you do not know the distance, you have
to sound.

Enter the distance to the medium which
your sensor has at 100 % filling.

Key

Display

1)
In case of two values which can be modified
you can move with the "OK“-key to the sec-
ond value.

Adjustment with medium
Fill the vessel e.g. to 10 %, enter in the menu
"

Min-adjustment“ with the "+“ and "–“ keys

10 % and confirm with the "OK“-key. Then fill
the vessel e.g. to 80 % or 100 %, enter in the
menu "

Max-adjustment“ with the "+“ and "–“

keys 80 % or 100 % and confirm with the
"OK“-key.

with
medium

Min.
adjust
at %

XXX.X

Max.
adjust
at %

XXX.X

1)