Technical Information
VEGAMET 407 Z
Technical data
Power supply
Operating voltage
value
tolerance
frequency
Standard
230 V AC
+10 % –15 %
50 / 60 Hz
Options
110 V AC
130 V AC
+15 % –10 %
50 / 60 Hz
240 V AC
24 V AC
42 V AC
+15 % –10 %
50 / 60 Hz
48 V AC
16 … 60 V DC
Power consumption
approx. 6 VA
or 4 W
Measuring data
Supply voltage for capacitive
measuring electrode or
pressure transmitter
24 V (max. 26 V) short-circuit proof, galvanically isolated
Data transmission
analog
Connection cable
2-core, unscreened (standard line)
Resistance per conductor
max. 200
Ω
Valid measured values
2 … 22 mA
Fault signal at
< 2 mA; > 22 mA
Min. measuring distance
300
µ
A
Indication
LC-display
4-digit
Current output
Range
0 … 20 mA or 4 … 20 mA
Load
max. 750
Ω
Galvanical separation
to power supply unit and input
Resolution
0,05 % of range
Linearity error
0,05 % of range
Temperature error
0,06 % / 10 K of sensor
Voltage output 1
Range
0 … 10 V, max. 1 mA
Galvanical separation
to power supply unit and to input
Resolution
0,05 % of range
Linearity error
0,1 % of range
Temperature error
0,06 % / 10 K of sensor
Voltage output 2
Range
0 … 5 V, max. 1 mA
Galvanical separation
to power supply unit and to input
Resolution
0,05 % of range
Linearity error
0,1 % of range
Temperature error
0,06 % / 10 K of sensor
Fail safe relay
Relay data:
1 spdt
floating
Contact material
Ag CdO and Au plated
min.
turn-on voltage
10 mV
switching circuit
10
µ
A
AC
DC
max.
turn-on voltage
U = 250 V
U = 60 V
switching circuit
I = 2 A
I = 1 A
max.
breaking capacity
S = 125 VA
P = 54 W
Operating
Permissible operating temperat.
–20
°
C … +60
°
C
conditions
Storage and transport temperat.
–20
°
C … +70
°
C
Electrical
Protection
IP 40
protective measures
Protection class
II
Mechanical
Series
Panel mounting, housing plastic ABS light grey
data
Dimensions
W = 53 mm, H = 127 mm, D = 143 mm
Weight
approx. 700 g