VEGA VEGAMET 407 Z User Manual
Page 13

13
VEGAMET 407 Z
Parameter adjustment
Password
All parameters can be interrogated as previously
described and their data indicated on the display.
Data input can be inhibited by programming the
password.
Alarm signals
Indication
Reason
Result
Measuring results
< - 10 %
Input below minimum limit (flashing)
without fail safe
> 110 %
Input above maximum limit (flashing)
Error code
E1
Connection cables reversed on
with fail safe
short-circuit
E2
Line break
E3
Incomplete or incorrect adjustm. proced.
E4
(together with flashing mode segments)
E8.1 …
Fault during
Current output = 22 mA
E8.4
data transfer (acc. to STO)
Voltage output
= 11 V or 5,5 V
E9
Fault in the EEPROM-memory
Activate password ....................................................
• select mode - - - - in MODEFIELD
• program figure 1 in PARAMETER FIELD
• then store with button STO
Adjust password .......................................................
• select the mode required for parameter adjust-
ment in the MODEFIELD, in the example mode t
• select data input, the keyword
0 - -
0
is displayed
in the PARAMETER FIELD
• program
0407
as password
• then store with button STO
• the parameter adjustment of e.g. mode t can be
made
(fail safe)