beautypg.com

VEGA VEGAPULS 56 Profibus PA User Manual

Page 78

background image

78

VEGAPULS 56 Profibus PA

Adjustment

- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in sensor or in external indicating instrument (optional)
- process adjustment interface PACTware

TM

- SIMATIC PDM in conjunction with Electronic Device Description (EDD)

Accuracy

(typical values under reference conditions)

2)

Accuracy

< 0.1 % (deviation in characteristics including
repeatability and hysteresis acc. to the limit
point adjustment relating to the max. measuring
range)

Linearity error

better than 0.05 %

Influence
- of the ambient temperature

2)

0.06 %/10 K

- of the process temperature

2)

negligible (0.004 %/10 K at 5 bar)
(0.003 %/10 K at 40 bar)

- of the process pressure

0.025 %/bar

Resolution of the digital output
signal

0.005 % (relating to max. measuring range)

Adjustment time

1 … 10 s (dependent on default setting)

Resolution

max. 1 mm

Characteristics

1)

Frequency

6.3 GHz (USA 6.3 GHz)

Intervals

0.6 s

Min. span between full
and empty adjustment

10 mm (recommended 50 mm)

Beam angle (at –3 dB)
- with DN 80

38° (only for standpipe measurement)

- with DN 100

30° (only for standpipe measurement)

- with DN 150

20°

- with DN 200

16°

- with DN 250

14°

Influence of the process temperature

at 0 bar nor measurable;
at 5 bar 0.004 %/10 °K;
at 40 bar 0.03 %/10 °K

Influence of the process pressure

0.0265 %/bar

Emitted radar power (average)

0.717 µW

Received average emitted power

3)

- distance 1 m

0.4 … 3.2 nW per cm

2

(0.4 … 3.2 x 10

-9

W/cm

3

)

- distance 5 m

0.02 … 0.13 nW per cm

2

Technical data