beautypg.com

VEGA VEGAPULS 56 Profibus PA User Manual

Page 64

background image

64

VEGAPULS 56 Profibus PA

Simulation

• Click to the menu "

Diagnostics/Simulation

Diagnostics/Simulation

Diagnostics/Simulation

Diagnostics/Simulation

Diagnostics/Simulation“

and choose the measurement loop.

Setup

The menu window "

Simulation of outputs“,

which is similar to the previous window,
opens. In this menu window however, you
can set the filling of the vessel, i.e. the meas-
ured value, and the display to any desired
value (simulation of measured value).

First of all, the actual measured value is dis-
played.

• Click to "Start

Start

Start

Start

Start“ in the turquoise window

segment.

The grey scroll bar becomes active. With this
scroll bar you can change the measured
value to any value in the range of
-10 % … 110 % and thereby simulate the
filling or emptying of the vessel. In the input
box of the turquoise window cutout you can
enter any percentage value of filling.

Note:

The simulated measured value is outputted
during adjustment with the PC until you stop
the simulation mode.