VEGAPULS 51K … 54K

21750-EN-031222

Diagnostics

6 Diagnostics

6.1 Simulation

To simulate a certain filling level, you can call
up the function “Simulation” in the adjustment
module MINICOM, in the adjustment software
PACT

ware

TM

or in the HART

®

handheld.

You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their adjustments and will
probably activate alarms or system func-
tions. One hour after the last simulation ad-
justment, the sensor returns automatically to
standard operating mode.

6.2 Error codes

Display

Meaning

Rectifying measure

E013

No valid measured value

Message is displayed during warm-up phase

- Sensor in the warm-up
phase
- Loss of the useful echo

If the message remains, a false echo storage
must be carried out with the adjustment module
MINICOM in the menu “sensor optimisation” or
better, with the PC and VVO.
If the message still remains, carry out a new
adjustment.

E017

Adjustment span too small

Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm.

E036

Sensor software does not

- Sensor must be programmed with new

run

software (service)
- Message appears during a software update.

E040

Hardware failure/Electronics

Check all connection cables.

defective

Contact our service department.