5 diagnostics, 1 simulation, 2 failure rectification – VEGA VEGAFLEX 51K User Manual
Page 30
30
VEGAFLEX 51K
5 Diagnostics
5.1 Simulation
For simulation of a certain filling, you can call up the function “Simulation” on the adjustment
module MINICOM, in the software program VVO or in the HART
®
handheld.
You simulate a certain current value. Please keep in mind that connected instruments, such as
e.g. a PLC, react according to their adjustments and will probably activate alarms or system
functions.
5.2 Failure rectification
Error
Corrective measure
E 013
Sensor does not find a
- Message is displayed during the warm-up
level echo
phase.
- If the message remains, the DK value of the
medium can be too low.
Check the useful and noise level.
See "4.2 Adjustment with adjustment module
MINICOM; 6. Useful and noise level“.
If the message still remains, carry out a new
adjustment.
E 017
Adjustment span too small
Carry out the adjustment again. Make sure that
the difference between min. and max. adjust-
ment is at least 10 mm.
E 036
Software update incorrect
Return the instrument for repair.
E 040
Hardware failure/
Check all connection cables.
Electronics defective
Contact our service department.
Diagnostics