beautypg.com

Danfoss MSV-F2 (DN 15-400) User Manual

Page 2

background image

DH-SMT/SI

VI.B1.B4.1E

© Danfoss 11/2007

2

1.0 Handling

1.1 Storage
- Storage temperature –20 to +65 °C dry;

free of dirt

- A desiccant or heating to prevent

condensation is necessary in damp
rooms.

- Don't damage the paintwork.

1.2 Transport
- Transport temperature –20 to + 65 °C.
- Protect against external force (impact,

vibration etc.).

- Don't damage the paintwork.

1.3 Handling before installation
- If flange covers are fitted, remove

shortly before maintenance !

- Protect against atmospheric conditions

e.g. wetness (applicate a desiccant).

- Correct handling protects against

damage.

2.0 Description

2.1 Scope of applications

Line regulating valves with a defined

characteristic for heating and cooling

systems. The plan designer is responsible

for selecting the correct valve for the

purpose.

Note: Do not use MSV-F2 valves for

handling steam!

2.2 Operating principles

The valve is closed (cone/seating function)

by turning the hand wheel clockwise.
- Position of the plug at DN 15 - 150 is

shown on two digit display. The outer
digit shows the basic setting and the
internal digit shows every tenth of the
turn. See Fig. 1.

- Position of the plug at DN 200 - 400 is

shown on the longitudinal scale. Fig. 2.

3.0 Installation

General notes on installation:
The following points should be taken into

account besides the general principles

governing installation work:
- Remove flange covers if present.
- There must be no foreign bodies inside

the valve or piping.

- Pay attention to the direction of flow:

see markings on the valve

- Valves can be installed with the spindle

pointing in any direction, but the
preferred spindle position is vertical.

- Reference for isolation:

If media-temperatures < ambient
temperatures - ask manufacturer.

- Installation upside down only if the

medium is clean.

- Centre packings between the flanges.
- Install measuring nipples before valve

is filled with water. See accessories in the
datasheet MSV-F2.

- Connection flanges must mate exactly.
- All parts must be free from stress after

installation.

- The valve must not serve as a fixed

point. It must be carried by the piping.

- Protect the valve from dirt, especially

during construction work.

- Install compensators to compensate for

thermal expansion of the piping.

- It is forbidden to heat the valve to

above its service temperature (see
data sheets), for instance by welding,
grinding, etc.

- To ensure that the valves function

correctly, the pipe run should be
straight for at least 5D upstream and 2D
downstream of the valve.

4.0 Presetting and locking the
handwheel

4.1: DN 15 - 150:
a: Position of the plug at DN 15 - 150 is

shown on two digit display. The outer
digit (a) shows the basic setting and the
internal digit (b) shows every tenth of
the turn. See Fig. 4.

b: Remove cover plug (c) by introducing

a screwdriver in the slot and gently
prising it out. See Fig. 5.

c: Turn the hand-wheel clockwise and

close the valve fully. Digital display
shall show 0,0. Turn the hand-wheel
counter clockwise to required value of
presetting by using the setting table
(i.e. 4,5, see Fig. 4).

d: Turn the inner adjustment screw (d)

clockwise until it seats. Use enclosed
3mm allen key for DN 15 - 50 and 4 mm
allen key (e) for DN 65 - 150. The valve
now can be closed, but not opened
more than the setting value. See Fig. 5.

e: Optionally you can lock the hand-wheel

and protect the setting. Fit the enclosed
clip (f) in the cut-out in the hand-wheel.
Thread the sealing wire (g) through the
holes on the clip, hand-wheel and lead
seal. Fit the lead seal. See Fig. 6.

4.2: DN 200 - 400
a: Turn the hand-wheel clockwise and close

the valve fully by hand (“0” position).

b: Unscrew the cap (h). See Fig. 7.
c: Turn the hand-wheel counter clockwise

to required value of presetting by using
the setting table.

d: Turn the stroke limiter (i) clockwise until it

seats. Protect it by fixing the lock nut (j).

e: Screw on the cap.

ENglISH