York AVY24 THRU 60 User Manual
Page 6
6
Johnson Controls Unitary Products
256819-YTG-J-1208
*
May be 0 (no breaker) or 1 (with breaker).
ELECTRICAL DATA - 208/230-1-60
Models
Heat Kits*
Max.
Static
Min.
Speed Tap
Total Heat
1
kW Staging
KW
MBH
W1 Only
W2 Only
W1 & W2
208v
230v
208v
230v
208v
230v
208v
230v
208v
230v
AVY24B**H21
4HK*6500206
0.5
Heat-D
1.9
2.5
6.4
8.5
1.9
2.5
1.9
2.5
1.9
2.5
4HK*6500506
0.5
Heat-D
3.6
4.8
12.3
16.4
3.6
4.8
3.6
4.8
3.6
4.8
4HK*6500806
0.5
Heat-C
5.6
7.5
19.2
25.6
2.8
3.75
5.6
7.5
5.6
7.5
4HK*6501006
0.5
Heat-B
7.2
9.6
24.6
32.8
3.6
4.8
7.2
9.6
7.2
9.6
4HK165N1506
0.5
Heat-A
10.8
14.4
36.9
49.1
3.6
4.8
7.2
9.6
10.8
14.4
AVY36C**H21
4HK*6500506
0.5
Heat-C
3.6
4.8
12.3
16.4
3.6
4.8
3.6
4.8
3.6
4.8
4HK*6500806
0.5
Heat-C
5.6
7.5
19.2
25.6
2.8
3.75
5.6
7.5
5.6
7.5
4HK*6501006
0.5
Heat-C
7.2
9.6
24.6
32.8
3.6
4.8
7.2
9.6
7.2
9.6
4HK16501506
0.5
Heat-C
10.8
14.4
36.9
49.1
3.6
4.8
7.2
9.6
10.8
14.4
4HK16501806
0.5
Heat-A
13.2
17.6
45.1
60.1
3.3
4.4
6.6
8.8
13.2
17.6
AVY48D**H21
SVY48D**N21
4HK*6500506
0.5
Heat-D
3.6
4.8
12.3
16.4
3.6
4.8
3.6
4.8
3.6
4.8
4HK*6500806
0.5
Heat-C
5.6
7.5
19.2
25.6
2.8
3.75
5.6
7.5
5.6
7.5
4HK*6501006
0.5
Heat-C
7.2
9.6
24.6
32.8
3.6
4.8
7.2
9.6
7.2
9.6
4HK16501506
0.5
Heat-C
10.8
14.4
36.9
49.1
3.6
4.8
7.2
9.6
10.8
14.4
4HK16501806
0.5
Heat-B
13.2
17.6
45.1
60.1
3.3
4.4
6.6
8.8
13.2
17.6
4HK16502006
0.5
Heat-B
14.4
19.2
49.2
65.5
3.6
4.8
7.2
9.6
14.4
19.2
4HK16502506
0.5
Heat-B
18.0
24.0
61.5
81.9
3.6
4.8
10.8
14.4
18.0
24
AVY60D**H21
SVY60D**N21
4HK*6500506
0.5
Heat-D
3.6
4.8
12.3
16.4
3.6
4.8
3.6
4.8
3.6
4.8
4HK*6500806
0.5
Heat-D
5.6
7.5
19.2
25.6
2.8
3.75
5.6
7.5
5.6
7.5
4HK*6501006
0.5
Heat-C
7.2
9.6
24.6
32.8
3.6
4.8
7.2
9.6
7.2
9.6
4HK16501506
0.5
Heat-C
10.8
14.4
36.9
49.1
3.6
4.8
7.2
9.6
10.8
14.4
4HK16501806
0.5
Heat-C
13.2
17.6
45.1
60.1
3.3
4.4
6.6
8.8
13.2
17.6
4HK16502006
0.5
Heat-C
14.4
19.2
49.2
65.5
3.6
4.8
7.2
9.6
14.4
19.2
4HK16502506
0.5
Heat-C
18.0
24.0
61.5
81.9
3.6
4.8
10.8
14.4
18.0
24
1. See conversion Table 10.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V
240V
.918
220V
240V
.840
COMFORT SETTINGS SELECTION
Delay Tap
Comfort Setting
A
Normal
B
Humid
C
Dry
D
Temperate