Temperature and flows – York YCAS0130 User Manual
Page 49

49
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
Excessive fl ow, above the max GPM,
will damage the evaporator.
MODEL
NUMBER
YCAS
LEAVING WATER
TEMPERATURE (°F)
EVAPORATOR FLOW
(GPM
3
)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0130EC
40
55
138
525
0
125
0140EC
40
55
138
525
0
125
0150EC
40
55
200
600
0
125
0160EC
40
55
200
600
0
125
0170EC
40
55
200
600
0
125
0180EC
40
55
200
600
0
125
0200EC
40
55
250
750
0
125
0210EC
40
55
250
750
0
125
0230EC
40
55
250
750
0
125
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK offi ce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK offi ce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
7