Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

YCJD42S41S1(H)

INDOOR COIL MODEL NO.

FC/MC/PC43

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1200

1400

1600

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

44.4 45.5 43.6 47.0 48.5 45.9 46.5 45.0 48.5 49.8 47.5 47.5 46.5 50.1 51.1

S.C.

41.5 35.6 29.7 28.7 21.5 42.9 37.5 31.4 30.2 22.9 44.4 39.4 33.2 31.7 24.3

KW

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6

75

T.C.

42.3 42.9 41.2 45.1 46.6 44.2 44.3 42.7 46.6 47.9 46.0 45.7 44.2 48.1 49.1

S.C.

39.4 35.2 29.2 28.5 21.3 41.1 37.4 31.1 30.1 22.4 42.9 39.7 33.0 31.8 23.6

KW

2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9

85

T.C.

40.2 40.3 38.9 43.3 44.6 42.4 42.1 40.4 44.7 45.9 44.6 43.9 41.9 46.0 47.2

S.C.

37.2 34.7 28.7 28.2 21.2 39.3 37.3 30.8 30.0 22.0 41.5 40.0 32.9 31.8 22.9

KW

3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1

95

T.C.

38.2 37.7 36.5 41.5 42.7 40.7 39.9 38.0 42.0 44.0 43.2 42.1 39.6 43.9 45.3

S.C.

35.0 34.3 28.1 28.0 21.0 37.5 37.3 30.5 29.4 21.6 40.0 40.3 32.8 31.9 22.2

KW

3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.3 3.4 3.3 3.3 3.3 3.4 3.4

105

T.C.

35.3 34.7 32.8 37.4 38.7 37.5 36.7 34.2 38.6 39.8 39.8 38.8 35.6 39.8 40.9

S.C.

32.3 32.1 26.5 26.4 19.6 34.5 34.5 28.8 28.4 20.4 36.7 37.0 31.1 30.5 21.2

KW

3.5 3.5 3.5 3.6 3.7 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.5 3.6 3.7

115

T.C.

32.4 31.7 29.2 33.4 34.8 34.5 33.6 30.5 34.6 35.7 36.5 35.5 31.8 35.7 36.7

S.C.

29.7 30.0 25.0 24.9 18.2 31.6 31.9 27.2 27.0 19.3 33.5 33.8 29.4 29.1 20.3

KW

3.7 3.7 3.7 3.8 4.0 3.8 3.8 3.7 3.8 4.0 3.8 3.8 3.7 3.9 4.0

125

T.C.

29.6 28.8 25.6 29.4 30.9 31.4 30.5 26.8 30.5 31.7 33.2 32.2 28.0 31.7 32.5

S.C.

27.1 27.9 23.5 23.4 16.8 28.7 29.3 25.6 25.6 18.1 30.2 30.6 27.6 27.8 19.4

KW

4.0 4.0 3.9 4.0 4.2 4.0 4.0 4.0 4.1 4.3 4.1 4.1 4.0 4.1 4.3

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

FC/MC/PC48

1.00 1.00 1.00

HC42

1.00 1.00 1.00

UC48

1.00 1.00 1.00

AHP42

0.97 1.00 0.97

MV16C

FC/MC43C

1.00 1.02 0.91

MA16C

FC/MC43C

1.00 1.00 1.00

MV16C

FC/MC48C

1.00 1.02 0.91

MV20D

FC/MC48D

1.00 1.02 0.91

MA14D

FC/MC48D

1.00 1.00 1.00

MA16C

FC/MC48C

1.00 1.00 1.00

F5FP048

1.00 1.00 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*B16

FC/MC/PC43B 1.00

1.01

0.91

PV8*C20

FC/MC/PC43C 1.00

1.02

0.91

P(C,V)9*C16

FC/MC/PC43C 1.00

1.01

1.00

P(C,V)9*C20

FC/MC/PC43C 1.00

1.02

0.91

PV8*C16

FC/MC/PC48C 1.00

1.01

0.91

PV8*C20

FC/MC/PC48C 1.00

1.02

0.91

P(C,V)9*C16

FC/MC/PC48C 1.00

1.01

1.00

P(C,V)9*C20

FC/MC/PC48C 1.00

1.02

0.91

P(C,V)9*D20

FC/MC/PC48D 1.00

1.02

0.91

PV8*C16

HC42 1.00

1.01

0.91

PV8*C20

HC42 1.00

1.02

0.91

P(C,V)9*C16

HC42 1.00

1.01

1.00

P(C,V)9*C20

HC42 1.00

1.02

0.91