York 090 User Manual
Page 4
279104-YTG-B-0307
4
Unitary Products Group
- = Not applicable
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL
ELECTRIC
2
HEAT KW
W
RATED
CFM
NET MBH
SEER
W/O TXV
SEER
WITH TXV
3
EER
TOTAL SENS.
3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD
E1RA036S(25,46)
MA12BN2,4
10
17
FC/MC35B3X
1250
34.4
25.3
10
–
8.95
MA12BN2,4
10
17
FC/MC36B3X
1250
34.4
25.3
10
–
8.95
MA12BN2,4
10
17
FC/MC42B3X
1250
34.4
25.3
10
–
8.95
N1AHC1646
10, 15
21
G2FD042(S,H)21
1250
34.2
25.3
10
–
8.95
E2RA048S(25,46
MA16CN4
10, 15
21
FC/MC48C3X
1600
45.5
33.7
10
–
9.45
MA20DN2
10, 15, 25
24
FC/MC48D3X
1725
45.5
33.7
10
–
9.45
MA20DN4
10, 15, 29
24
FC/MC48D3X
1725
45.5
33.7
10
–
9.45
N1AHC1646
10, 15
21
G2FD048(S,H)21
1600
45.5
33.7
10
–
9.45
N1AHD2046
10, 15, 29
24
G2FD048(S,H)24
1600
45.5
33.7
10
–
9.45
E1RA060S(25,46)
MA20DN4
10, 15, 29
24
FC/MC60D3X
2000
57.0
41.0
10
–
9.80
N1AHD2046
10, 15, 29
24
G2FD048(S,H)24
1700
57.0
41.0
10
–
9.80
3 PH 10 SEER HP WITH AHP / SHP / F2RP / RC / FP / FC
4,5
E1RA036S25
F2RP/FP036
5, 8, 10, 15, 19
21
–
1250
34.0
24.9
10
–
9.00
F2RD/FP042
5, 8, 10, 15
21
–
1250
34.0
25.6
10
–
9.00
AHP36C3X
10, 15
21
–
1250
34.0
25.6
10
–
9.00
AHP42C3X
10, 15, 18
21
–
1250
34.0
25.6
10
–
9.00
E2RA048S25
F2FP048
5, 8, 10, 15, 20, 25
24
–
1600
45.0
33.5
10
–
9.40
F2FP060
5, 8, 10, 15, 20, 25
24
–
1600
46.5
34.4
10
–
9.60
AHP/SHP48D3X
10, 15, 18
24
–
1600
46.5
34.4
10
–
9.60
E1RA060S25
F2FP060
5, 8, 10, 15, 20, 25
24
–
1700
56.0
40.0
10
–
9.40
AHP/SHP60D3X
10, 15
24
–
1700
56.0
40.0
10
–
9.40
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 8
0°F entering air temperature, 50% RH, and rated air flow.
KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input
in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
.
models. All ratings remain the same.
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D. standard.