York 090 User Manual
Page 12
279104-YTG-B-0307
12
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
E1RA036S(25,46)
EVAPORATOR COIL MODEL NO
F2RP/F2FP036
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1000
1250
1400
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
41.6
3.37
3.62
42.0
3.30
3.73
41.3
3.27
3.70
70
39.1
3.54
3.24
40.2
3.49
3.37
40.2
3.49
3.38
80
37.4
3.70
2.97
39.1
3.67
3.12
39.7
3.69
3.16
47
60
35.3
3.17
3.26
35.7
3.15
3.32
34.8
3.15
3.24
70
33.1
3.32
2.93
34.0
3.32
3.00
33.8
3.33
2.98
80
31.5
3.46
2.67
32.7
3.48
2.76
33.3
3.49
2.80
40
60
30.2
3.02
2.94
31.2
3.03
3.02
31.9
3.05
3.08
70
28.7
3.14
2.68
29.5
3.16
2.74
30.4
3.18
2.81
80
27.1
3.28
2.43
27.9
3.30
2.48
28.9
3.32
2.55
30
60
26.1
2.89
2.65
27.4
2.93
2.74
27.5
2.96
2.73
70
24.4
2.96
2.42
25.8
3.01
2.51
26.1
3.04
2.51
80
22.4
3.07
2.14
23.8
3.13
2.23
24.3
3.16
2.25
17
60
21.4
2.66
2.36
21.9
2.71
2.37
22.0
2.74
2.36
70
19.7
2.73
2.12
20.4
2.79
2.15
20.7
2.82
2.15
80
18.0
2.79
1.89
18.9
2.86
1.94
19.3
2.89
1.96
10
60
18.1
2.50
2.12
18.8
2.56
2.16
19.1
2.60
2.16
70
16.5
2.55
1.90
17.4
2.62
1.95
17.7
2.66
1.96
80
14.8
2.58
1.68
15.8
2.65
1.75
16.2
2.69
1.77
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MA12BN2,4
FC/MC35B3X
1.01
1.02
1.01
MA12BN2,4
FC/MC36B3X
1.01
1.02
1.01
MA12BN2,4
FC/MC42B3X
1.01
1.02
1.01
MA12BN2,4
G2FD042(S,H)21
1.00
1.00
1.00
AHP42C3X
–
1.00
1.00
1.00
F2RP/F2FP042
–
1.00
1.00
1.00
–
G1FA048S21
1.00
1.00
1.00
–
G1NA036S17L
1.03
0.97
1.07
–
G1NA048S21D
1.03
0.97
1.07
–
FC/MC/PC35*3X
1.01
0.99
1.01
–
FC/MC/PC/UC36*3X
1.01
0.99
1.01
–
FC/MC/PC-UC42*3X
1.01
0.99
1.01
–
G1UA048S21
1.00
1.00
1.00
–
G2FD042(S,H)21
1.00
1.00
1.00