York YZE024 THRU 060 User Manual
Page 27
Johnson Controls Unitary Products
27
246750-YTG-L-0408
Multipliers for determining the performance with other indoor sections.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
HEATING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
YZE06011
INDOOR COIL MODEL NO.
MC61D + MV20D
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1750
1850
1950
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
64.0 4.5 4.2 64.6 4.5 4.2 65.2 4.5 4.3
70
62.8 5.0 3.7 63.3 4.9 3.7 63.8 4.9 3.8
80
61.5 5.4 3.3 61.9 5.4 3.4 62.4 5.4 3.4
47
60
55.7 4.2 3.9 55.9 4.2 3.9 56.2 4.2 3.9
70
54.1 4.6 3.4 54.5 4.6 3.5 54.9 4.6 3.5
80
52.5 5.0 3.1 53.1 5.0 3.1 53.6 5.0 3.1
40
60
49.5 4.0 3.7 49.0 4.0 3.6 48.6 4.0 3.6
70
42.4 4.2 2.9 45.2 4.3 3.1 48.1 4.4 3.2
80
35.2 4.5 2.3 41.4 4.7 2.6 47.5 4.9 2.9
30
60
42.5 3.8 3.3 39.9 3.7 3.1 37.3 3.7 2.9
70
38.8 4.0 2.8 39.1 4.1 2.8 39.4 4.2 2.8
80
35.0 4.3 2.4 38.3 4.5 2.5 41.6 4.6 2.6
17
60
34.3 3.6 2.8 32.3 3.5 2.7 30.4 3.4 2.6
70
34.2 4.1 2.4 32.6 4.0 2.4 31.0 3.9 2.3
80
34.0 4.6 2.2 32.9 4.5 2.1 31.7 4.5 2.1
10
60
30.5 3.4 2.6 31.1 3.4 2.7 31.7 3.5 2.7
70
29.4 3.8 2.3 29.2 3.8 2.3 29.0 3.7 2.3
80
28.2 4.1 2.0 27.3 4.1 2.0 26.4 4.0 1.9
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
F*FV060
–
1.00 1.00 1.00
AV60
–
1.00 1.00 1.00
MV20D
FC/MC60D
1.00 1.00 1.00
MV20D
FC/MC62D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*D20
FC/MC/PC60D
0.99 0.99 1.00
P(C,V)9*D20
FC/MC62D
0.99 0.99 1.00
PV8*C20
FC/PC60C
0.99 0.99 1.00
P(C,V)9*C20
FC/PC60C
0.99 0.99 1.00
P(C,V)9*D20
HC60
0.99 0.99 1.00
PV8*C20
HD60
0.99 0.99 1.00
P(C,V)9*D20
HD60
0.99 0.99 1.00
P(C,V)9*D20
FC/MC62D
0.99 0.99 1.00
P(C,V)9*C20
UC60C
0.99 0.99 1.00
PV8*C20
UC60C
0.99 0.99 1.00
P(C,V)9*D20
UC60D
0.99 0.99 1.00