beautypg.com

York YZE024 THRU 060 User Manual

Page 24

background image

24

Johnson Controls Unitary Products

246750-YTG-L-0408

Multipliers for determining the performance with other indoor sections.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

YZE04811

INDOOR COIL MODEL NO.

FC/MC/PC60D + MV20D

AIR TEMP.

ENTERING
OUTDOOR

UNIT

AIR TEMP.

ENTERING

INDOOR

COIL

ID CFM

950

1000

1050

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

60

60

38.9 2.5 4.6 39.3 2.5 4.7 39.8 2.4 4.8

70

37.6 2.8 4.0 37.8 2.7 4.1 38.1 2.7 4.2

80

36.2 3.1 3.4 36.3 3.0 3.6 36.4 2.9 3.7

47

60

33.1 2.4 4.1 33.2 2.3 4.2 33.4 2.3 4.3

70

31.3 2.6 3.5 31.8 2.6 3.6 32.3 2.6 3.7

80

29.6 2.9 3.0 30.4 2.8 3.1 31.2 2.8 3.2

40

60

29.4 2.3 3.7 29.7 2.3 3.8 29.9 2.3 3.9

70

28.4 2.7 3.1 28.7 2.6 3.2 28.9 2.6 3.3

80

27.4 3.0 2.7 27.7 2.9 2.8 28.0 2.9 2.8

30

60

25.6 2.2 3.4 25.5 2.2 3.4 25.5 2.2 3.4

70

24.3 2.6 2.8 24.3 2.6 2.8 24.3 2.6 2.8

80

23.0 2.9 2.3 23.0 2.9 2.3 23.1 2.9 2.3

17

60

19.7 2.3 2.6 19.6 2.2 2.6 19.4 2.2 2.6

70

17.3 2.6 2.0 17.2 2.5 2.0 17.0 2.5 2.0

80

15.0 2.9 1.5 14.8 2.8 1.6 14.6 2.7 1.6

10

60

15.9 2.2 2.1 15.9 2.2 2.1 15.9 2.2 2.1

70

14.9 2.5 1.7 15.0 2.5 1.8 15.0 2.5 1.8

80

13.9 2.8 1.4 14.0 2.8 1.5 14.1 2.7 1.5

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

MBH

KW

COP

F*FV060

1.00 1.01 0.99

AV48

1.00 1.01 0.99

AV60

1.00 1.00 1.00

MV20D

FC/MC60D

1.00 1.01 0.99

MV20D

FC/MC62D

1.00 1.01 0.99

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

P(C,V)9*D20

FC/MC/PC60D

0.98 0.99 0.99

P(C,V)9*D20

FC/MC62D

0.98 0.99 0.99

PV8*C20

FC/PC60C

0.98 0.99 0.99

P(C,V)9*C20

FC/PC60C

0.98 0.99 0.99

P(C,V)9*D20

HC60

0.98 0.99 0.99

PV8*C20

HC60

0.98 0.99 0.99

P(C,V)9*D20

HD60

0.98 0.99 0.99

P(C,V)9*D20

FC/MC62D

0.98 0.99 0.99

P(C,V)9*C20

UC60C

0.98 0.99 0.99

PV8*C20

UC60C

0.98 0.99 0.99

P(C,V)9*D20

UC60D

0.98 0.99 0.99