beautypg.com

York YZE024 THRU 060 User Manual

Page 15

background image

Johnson Controls Unitary Products

15

246750-YTG-L-0408

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

HIGH CFM

COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

YZE03611

INDOOR COIL MODEL NO.

FC/MC48C + MV16C

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

1100

1200

1300

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

57

62

62

67

72

57

65

T.C.

31.6 36.2 37.2 37.3 38.5 33.1 36.3 37.6 37.4 38.3 34.7 36.5 37.9 37.6 38.1

S.C.

31.2 30.3 26.6 24.5 19.1 32.9 31.3 27.6 24.9 19.3 34.5 32.3 28.5 25.4 19.5

K.W.

1.9 2.0 2.1 2.0 2.1 2.0 2.0 2.1 2.0 2.1 2.0 2.0 2.1 2.0 2.1

75

T.C.

30.9 34.6 35.3 36.5 38.4 32.4 34.9 35.7 36.8 38.3 33.9 35.2 36.0 37.0 38.1

S.C.

30.7 29.7 25.8 24.4 19.4 32.1 30.8 26.8 25.1 19.6 33.5 31.9 27.7 25.8 19.8

K.W.

2.2 2.3 2.3 2.3 2.4 2.2 2.3 2.3 2.3 2.4 2.3 2.3 2.4 2.3 2.4

85

T.C.

30.3 33.1 33.4 35.7 38.3 31.7 33.5 33.8 36.1 38.2 33.0 34.0 34.1 36.4 38.2

S.C.

30.1 29.1 25.0 24.4 19.7 31.3 30.4 26.0 25.2 19.9 32.4 31.6 26.9 26.1 20.2

K.W.

2.5 2.5 2.5 2.6 2.6 2.5 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.7

95

T.C.

29.7 31.6 31.5 34.9 38.1 30.9 32.1 31.9 35.4 38.2 32.2 32.7 32.2 35.9 38.3

S.C.

29.5 28.5 24.2 24.4 20.0 30.4 29.9 25.2 25.4 20.2 31.4 31.2 26.1 26.4 20.5

K.W.

2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.9 2.8 2.9 3.0

105

T.C.

28.2 29.7 29.6 32.5 35.8 29.3 30.3 29.9 33.0 36.0 30.4 30.9 30.2 33.5 36.2

S.C.

28.0 27.2 23.2 23.3 19.0 28.8 28.5 23.9 24.3 19.4 29.7 29.7 24.6 25.3 19.7

K.W.

3.2 3.2 3.2 3.3 3.3 3.2 3.3 3.2 3.3 3.4 3.3 3.3 3.2 3.3 3.4

115

T.C.

26.7 27.9 27.7 30.2 33.5 27.7 28.5 28.0 30.7 33.8 28.6 29.1 28.3 31.2 34.2

S.C.

26.6 26.0 22.3 22.3 18.0 27.3 27.1 22.7 23.3 18.5 28.0 28.1 23.1 24.3 19.0

K.W.

3.6 3.7 3.6 3.7 3.8 3.7 3.7 3.6 3.7 3.8 3.7 3.7 3.6 3.8 3.8

125

T.C.

25.3 26.0 25.9 27.9 31.2 26.0 26.7 26.2 28.4 31.7 26.8 27.3 26.4 29.0 32.2

S.C.

25.1 24.7 21.3 21.3 17.0 25.7 25.7 21.5 22.3 17.6 26.3 26.6 21.6 23.2 18.2

K.W.

4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.0 4.2 4.2

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV36

1.00 1.00 1.00

AV48

1.00 1.00 1.00

MV12B

FC/MC35B

0.99 0.93 1.01

MV12B

FC/MC42B

0.99 0.93 1.01

MV16C

FC/MC48C

1.00 1.00 1.00

MV12D

FC/MC48D

1.00 1.00 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

P(C,V)9*B12

FC/MC/PC35B

1.01 0.94 1.03

PV8*B16

FC/MC/PC35B

1.01 0.94 1.03

P(C,V)9*C16

FC/MC/PC35C

1.01 0.94 1.03

PV8*C16

FC/MC/PC35C

1.01 0.94 1.03

PV8*C20

FC/MC/PC35C

1.01 0.94 1.03

P(C,V)9*C20

FC/MC/PC35C

1.01 0.94 1.03

PV8*B16

FC/MC/PC42B

1.01 0.94 1.03

P(C,V)9*B12

FC/MC/PC42B

1.09 0.91 1.12

P(C,V)9*C20

FC/MC/PC42C

1.01 0.94 1.03

P(C,V)9*C16

FC/MC/PC42C

1.01 0.94 1.03

PV8*C16

FC/MC/PC42C

1.09 0.91 1.12

PV8*C20

FC/MC/PC42C

1.09 0.91 1.12

P(C,V)9*C20

FC/MC/PC48C

1.05 1.02 1.05

P(C,V)9*C16

FC/MC/PC48C

1.05 1.02 1.05

PV8*C16

FC/MC/PC48C

1.11 1.00 1.11

PV8*C20

FC/MC/PC48C

1.11 1.00 1.11

P(C,V)9*D20

FC/MC/PC48D

1.11 1.00 1.11

PV8*C16

HC42

1.05 1.02 1.05

PV8*C20

HC42

1.05 1.02 1.05

PV8*B16

UC42B

1.05 1.02 1.05

P(C,V)9*B12

UC42B

1.05 1.02 1.05

PV8*C20

UC42C

1.05 1.02 1.05

PV8*C16

UC42C

1.05 1.02 1.05

P(C,V)9*C16

UC42C

1.05 1.02 1.05

P(C,V)9*C20

UC42C

1.05 1.02 1.05

P(C,V)9*C20

UC48C

1.05 1.02 1.05

PV8*C20

UC48C

1.05 1.02 1.05

PV8*C16

UC48C

1.05 1.02 1.05

P(C,V)9*C16

UC48C

1.05 1.02 1.05

P(C,V)9*D20

UC48D

1.05 1.02 1.05

Variable Speed
Furnace

Coil

T.C.

S.C.

KW