York YZE024 THRU 060 User Manual
Page 15
Johnson Controls Unitary Products
15
246750-YTG-L-0408
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
YZE03611
INDOOR COIL MODEL NO.
FC/MC48C + MV16C
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1100
1200
1300
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
31.6 36.2 37.2 37.3 38.5 33.1 36.3 37.6 37.4 38.3 34.7 36.5 37.9 37.6 38.1
S.C.
31.2 30.3 26.6 24.5 19.1 32.9 31.3 27.6 24.9 19.3 34.5 32.3 28.5 25.4 19.5
K.W.
1.9 2.0 2.1 2.0 2.1 2.0 2.0 2.1 2.0 2.1 2.0 2.0 2.1 2.0 2.1
75
T.C.
30.9 34.6 35.3 36.5 38.4 32.4 34.9 35.7 36.8 38.3 33.9 35.2 36.0 37.0 38.1
S.C.
30.7 29.7 25.8 24.4 19.4 32.1 30.8 26.8 25.1 19.6 33.5 31.9 27.7 25.8 19.8
K.W.
2.2 2.3 2.3 2.3 2.4 2.2 2.3 2.3 2.3 2.4 2.3 2.3 2.4 2.3 2.4
85
T.C.
30.3 33.1 33.4 35.7 38.3 31.7 33.5 33.8 36.1 38.2 33.0 34.0 34.1 36.4 38.2
S.C.
30.1 29.1 25.0 24.4 19.7 31.3 30.4 26.0 25.2 19.9 32.4 31.6 26.9 26.1 20.2
K.W.
2.5 2.5 2.5 2.6 2.6 2.5 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.7
95
T.C.
29.7 31.6 31.5 34.9 38.1 30.9 32.1 31.9 35.4 38.2 32.2 32.7 32.2 35.9 38.3
S.C.
29.5 28.5 24.2 24.4 20.0 30.4 29.9 25.2 25.4 20.2 31.4 31.2 26.1 26.4 20.5
K.W.
2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.9 2.8 2.9 3.0
105
T.C.
28.2 29.7 29.6 32.5 35.8 29.3 30.3 29.9 33.0 36.0 30.4 30.9 30.2 33.5 36.2
S.C.
28.0 27.2 23.2 23.3 19.0 28.8 28.5 23.9 24.3 19.4 29.7 29.7 24.6 25.3 19.7
K.W.
3.2 3.2 3.2 3.3 3.3 3.2 3.3 3.2 3.3 3.4 3.3 3.3 3.2 3.3 3.4
115
T.C.
26.7 27.9 27.7 30.2 33.5 27.7 28.5 28.0 30.7 33.8 28.6 29.1 28.3 31.2 34.2
S.C.
26.6 26.0 22.3 22.3 18.0 27.3 27.1 22.7 23.3 18.5 28.0 28.1 23.1 24.3 19.0
K.W.
3.6 3.7 3.6 3.7 3.8 3.7 3.7 3.6 3.7 3.8 3.7 3.7 3.6 3.8 3.8
125
T.C.
25.3 26.0 25.9 27.9 31.2 26.0 26.7 26.2 28.4 31.7 26.8 27.3 26.4 29.0 32.2
S.C.
25.1 24.7 21.3 21.3 17.0 25.7 25.7 21.5 22.3 17.6 26.3 26.6 21.6 23.2 18.2
K.W.
4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.0 4.2 4.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AV36
–
1.00 1.00 1.00
AV48
–
1.00 1.00 1.00
MV12B
FC/MC35B
0.99 0.93 1.01
MV12B
FC/MC42B
0.99 0.93 1.01
MV16C
FC/MC48C
1.00 1.00 1.00
MV12D
FC/MC48D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*B12
FC/MC/PC35B
1.01 0.94 1.03
PV8*B16
FC/MC/PC35B
1.01 0.94 1.03
P(C,V)9*C16
FC/MC/PC35C
1.01 0.94 1.03
PV8*C16
FC/MC/PC35C
1.01 0.94 1.03
PV8*C20
FC/MC/PC35C
1.01 0.94 1.03
P(C,V)9*C20
FC/MC/PC35C
1.01 0.94 1.03
PV8*B16
FC/MC/PC42B
1.01 0.94 1.03
P(C,V)9*B12
FC/MC/PC42B
1.09 0.91 1.12
P(C,V)9*C20
FC/MC/PC42C
1.01 0.94 1.03
P(C,V)9*C16
FC/MC/PC42C
1.01 0.94 1.03
PV8*C16
FC/MC/PC42C
1.09 0.91 1.12
PV8*C20
FC/MC/PC42C
1.09 0.91 1.12
P(C,V)9*C20
FC/MC/PC48C
1.05 1.02 1.05
P(C,V)9*C16
FC/MC/PC48C
1.05 1.02 1.05
PV8*C16
FC/MC/PC48C
1.11 1.00 1.11
PV8*C20
FC/MC/PC48C
1.11 1.00 1.11
P(C,V)9*D20
FC/MC/PC48D
1.11 1.00 1.11
PV8*C16
HC42
1.05 1.02 1.05
PV8*C20
HC42
1.05 1.02 1.05
PV8*B16
UC42B
1.05 1.02 1.05
P(C,V)9*B12
UC42B
1.05 1.02 1.05
PV8*C20
UC42C
1.05 1.02 1.05
PV8*C16
UC42C
1.05 1.02 1.05
P(C,V)9*C16
UC42C
1.05 1.02 1.05
P(C,V)9*C20
UC42C
1.05 1.02 1.05
P(C,V)9*C20
UC48C
1.05 1.02 1.05
PV8*C20
UC48C
1.05 1.02 1.05
PV8*C16
UC48C
1.05 1.02 1.05
P(C,V)9*C16
UC48C
1.05 1.02 1.05
P(C,V)9*D20
UC48D
1.05 1.02 1.05
Variable Speed
Furnace
Coil
T.C.
S.C.
KW