Battery interconnection –9, Series –9, Battery interconnection – Xantrex Technology 10 User Manual
Page 47
Batteries
975-0251-01-01
3–9
No Maintenance
There is no need to add water and the tops of the batteries stay clean. Also the
batteries can be used in any position and are Coast Guard approved for use
without a battery box.
Low Self-Discharge
Rate
Unlike wet cell batteries, the gel cell will hold its charge for months if left sitting
with no load and no float charge. They can be stored in the off-season without a
constant float charge and without fear of freezing.
Low Internal
Resistance
The result of this is a higher battery voltage under load, which will result in better
inverter performance on demanding high power loads. In addition this allows the
gel cell to accept a high rate of charge, a plus for rapid recharging.
No Sulfation
The combination of acids in the gel cell prevents sulfation and eliminates the need
for battery equalization.
The result of these features is a battery that solves many common problems. Cycle
life is high, even under constant deep discharging. For all these reasons the gel
cell is highly recommended.
Battery Interconnection
In most cases, you will be using a bank of two or more batteries with your
inverter/charger. You may connect batteries together in two configurations: series
and parallel.
Series
Connecting two batteries in series will double the voltage of the battery bank.
For instance, two 6-volt batteries connected in series will produce 12 volts; four in
series will produce 24-volts. The amp hour capacity of the battery bank will be the
same as each individual battery. As an example, two 6-volt, 220 amp-hour
batteries in series will produce one 12-volt, 220 amp-hour battery bank.
Figure 3-5 Series Battery Connection
+
+
–
–