beautypg.com

Ac wiring –18, Ac wiring – Xantrex Technology 10 User Manual

Page 34

background image

Installation

2–18

975-0251-01-01

AC Wiring

Use a screwdriver to remove the screws that secure the AC wiring compartment
cover plate.

Inside you will see that the compartment is divided into two sections, one labeled
AC INPUT, the other labeled AC OUTPUT. Each side contains three pigtails:
brown, blue, green/yellow. Wire nut connectors are provided.

Two AC wiring knockouts are provided on the AC compartment cover plate. After
removing the knockouts, you can add strain reliefs for additional stability or
conduit fittings if the wiring will be routed through conduit. Flexible conduit is
recommended.

You must use 2.5 mm

2

ES copper wire with insulation rated for 60 degrees

centigrade or higher for both the AC input and AC output.

Figure 2-10 AC Compartment Cover Plate Screws

Remove these screws

Wire Nut Connectors

Wire Color

Description

Brown

Hot or Line

Blue

Neutral

Green/Yellow

Ground

Solid Green (AC output only)

Internal output neutral to ground bonding conductor

Important:

At the AC output, the green/yellow and solid green wires are already

connected together.