Remote Control Panel

975-0251-01-01

3–5

Equalize or Three-Stage Charging (Switch #1)

Cycling this switch

ON

for 1

second, then

OFF

, will initiate an equalizing charge cycle. The battery charger

must be engaged before cycling the switch. The switch must always be left in the

OFF

position. If it is left

ON

, an equalizing charge cycle will initiate every time the

charger is engaged - this could cause battery damage. The equalizing cycle is
timed to last 8 hours from the time the switch is cycled, at which point the charger
resumes normal charging in the float stage. The BATTERY LED blinks when
equalizing. Refer to page 3–14 for a discussion of the theory and procedure for
battery equalizing.

Battery Type (Switch #2 and 3)

Gel cell and wet cell batteries have slightly

different charge voltage requirements and optimum battery charging is
temperature dependent. For these reasons, the DIP switches allow four different
battery charger voltage set points, depending on battery type and ambient
temperature:

See page 3–16 for the specific voltages for each setting.

Auto Charge (Switch #4)

With the switch in the

OFF

position, the remote panel

ON

/

OFF

switch only controls the inverter operation. With the switch turned

ON

, this

switch allows the power

ON

/

OFF

switch on the front of the remote to control the

battery charger as well as the inverter.

Figure 3-4 Freedom Remote Control Dip Switches

Battery Type and
Temperature

Switch Position
Switch 2

Switch 3

Cool Wet Cell (< 27 °C)

Off

Off

Warm Wet Cell (> 27 °C) On

Off

Cool Gel Cell (< 27 °C)

Off

On

Warm Gel Cell (> 27 °C)

On

On