beautypg.com

Table 5: cooling capacities - 3 ton (dee / deg036), 5 cooling capacities - 3 ton (dee / deg036), Nominal rating all sensible capacity – York SUNLINE PLUS D1EE036 User Manual

Page 8

background image

036-21411-002-A-0204

8

Unitary Products Group

TABLE 5: COOLING CAPACITIES - 3 TON (DEE / DEG036)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

85°F

95°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

kW

SENSIBLE CAPACITY

1

, MBH

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

ENTERING DRY BULB, °F

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1500

72

55

3.4

35

31

26

22

18

-

-

51

3.7

35

30

26

21

17

-

-

67

52

3.3

47

42

38

33

29

24

20

48

3.6

45

41

36

32

28

23

19

62

42

3.2

42

42

42

37

33

28

24

39

3.5

39

39

39

34

30

25

21

57

42

3.2

42

42

42

38

33

29

24

39

3.5

39

39

39

35

30

26

21

1350

72

51

3.3

32

28

24

20

16

-

-

49

3.6

32

28

24

20

16

-

-

67

49

3.3

42

38

34

30

26

22

18

47

3.5

42

38

34

30

26

22

18

62

39

3.2

39

39

37

33

29

25

21

37

3.5

37

37

37

33

29

25

21

57

40

3.2

40

40

38

34

30

26

22

38

3.5

38

38

38

34

30

26

22

1200

72

48

3.2

28

24

21

17

14

-

-

48

3.6

29

25

22

18

15

-

-

67

46

3.3

37

34

30

27

23

19

16

46

3.5

39

36

32

38

25

21

18

62

36

3.2

36

36

33

29

26

22

19

36

3.5

36

36

35

31

28

24

21

57

37

3.2

37

37

35

31

27

24

20

37

3.4

37

37

37

33

30

26

22

1050

72

46

3.3

26

23

19

16

13

-

-

45

3.6

26

23

20

16

13

-

-

67

44

3.3

34

31

28

25

22

18

15

43

3.5

35

32

28

25

22

19

16

62

35

3.2

35

34

31

28

24

21

18

34

3.4

34

33

31

28

25

22

19

57

36

3.2

36

35

32

29

26

23

20

35

3.4

35

34

33

30

27

23

20

900

72

45

3.3

24

21

18

15

13

-

-

43

3.5

23

20

17

15

12

-

-

67

42

3.2

31

29

26

23

20

17

15

40

3.5

30

28

25

22

19

16

14

62

34

3.2

34

32

26

26

23

20

18

32

3.4

32

30

28

25

22

19

17

57

35

3.1

35

33

30

27

25

22

19

33

3.4

33

32

29

26

24

21

18

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F

115°F

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

ENTERING DRY BULB, °F

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1500

72

47

3.9

33

29

25

20

16

-

-

43

4.1

32

28

23

19

14

-

-

67

44

3.8

43

39

35

30

26

22

17

40

4.1

40

38

33

29

24

20

16

62

36

3.7

36

36

36

31

27

22

18

33

4.0

33

33

33

28

24

19

15

57

36

3.7

36

36

36

31

27

23

18

33

3.9

33

33

33

28

24

20

15

1350

72

44

3.9

30

26

22

18

14

-

-

39

4.1

28

24

20

16

12

-

-

67

42

3.8

39

36

32

28

24

20

16

37

4.0

36

33

29

25

21

17

13

62

34

3.7

34

34

33

29

25

21

17

30

4.0

30

30

30

26

22

18

14

57

34

3.7

34

34

34

30

26

22

18

30

3.9

30

30

31

27

23

19

15

1200

72

42

3.8

27

23

20

16

12

-

-

36

4.1

24

21

17

14

10

-

-

67

40

3.8

36

32

29

25

22

18

14

34

4.0

33

29

25

22

18

15

11

62

32

3.7

32

32

31

28

24

20

17

27

3.9

27

27

28

24

20

17

13

57

32

3.7

32

32

33

29

26

22

19

28

3.9

28

28

29

26

22

18

15

1050

72

40

3.8

24

21

18

15

12

-

-

35

4.1

22

19

16

13

10

-

-

67

38

3.7

32

29

26

23

19

16

13

33

4.0

30

26

23

20

17

14

11

62

30

3.7

30

30

28

25

22

19

16

27

3.9

27

27

26

22

19

16

13

57

31

3.6

31

31

30

27

24

20

17

27

3.9

27

27

27

24

21

17

14

900

72

38

3.8

22

19

16

13

11

-

-

34

4.0

20

18

15

12

9

-

-

67

36

3.7

29

26

23

20

17

15

12

32

4.0

27

24

21

18

16

13

10

62

29

3.6

29

28

26

23

20

17

15

26

3.9

26

26

24

21

18

15

13

57

30

3.6

30

29

27

24

21

19

16

26

3.9

26

26

25

22

19

17

14

1.

These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 8 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2.

These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to Table 8 or 11 for the kW of the supply air blower motor.

NOMINAL RATING

ALL SENSIBLE CAPACITY

This manual is related to the following products: