beautypg.com

York LY8S User Manual

Page 6

background image

036-21618-003 Rev. A (1205)

6

Unitary Products Group

HORIZONTAL SIDEWALL VENTING

For applications where vertical venting is not possible, the
only approved method of horizontal venting is the use of an
auxiliary power vent. Approved power venters are Fields
Controls Model SWG-4Y or Tjernlund Model GPAK-JT. Fol-
low all application and installation details provided by the
manufacturer of the power vent. This unit may be horizontally
vented using 4” (10.2 cm) diameter pipe with a minimum
length of 4.5 feet (1.37 m) and a maximum length of 34.5 feet
(10.82 m) with up to 4 elbows.

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE: The filter pressure drop values in the “Filter Perfor-
mance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.

NOTES:

1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
2. Air flows above 1800 CFM require either return from two sides or
one side plus bottom.

FILTER SIZES

CFM

Cabinet

Size

Side

(in)

Bottom

(in)

1200

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

1600

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

(2) 16 x 25

20 x 25

2200

C

(2) 16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.

Airflow

Range

Minimum

Opening Size

Filter Type

Disposable

Washable Fibers

Pleated

1 Opening

2 Openings

1 Opening

2 Openings

1 Opening

2 Openings

1 Opening

2 Openings

CFM

In³

In³

inwc

inwc

inwc

inwc

inwc

inwc

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.05

0.05

0.2

1001 - 1250

330

0.1

0.1

0.2

1251 - 1500

330

0.1

0.1

0.25

1501 - 1750

380

658

0.15

0.09

0.14

0.08

0.3

0.17

1751 - 2000

380

658

0.19

0.11

0.18

0.1

0.3

0.17

2001 & Above

463

658

0.19

0.11

0.18

0.1

0.3

0.17

UNIT CLEARANCES TO COMBUSTIBLES (ALL DIMENSIONS IN INCHES, AND ALL SURFACES IDENTIFIED WITH THE
UNIT IN AN UPFLOW CONFIGURATION)

Application

Top

Front

Rear

Left

Side

Right

Side

Flue

Floor/

Bottom

Closet

Alcove

Attic

Line

Contact

Upflow

1

6

0

0

3

6

Combustible

Yes

Yes

Yes

No

Upflow B-Vent

1

3

0

0

0

1

Combustible

Yes

Yes

Yes

No

Horizontal

1

6

0

0

3

6

Combustible

No

Yes

Yes

Yes

1

Horizontal B-Vent

1

3

0

0

0

1

Combustible

No

Yes

Yes

Yes

1

1. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal postion) of the furance jacket

and building joists, studs or framing.