beautypg.com

York 10 SEER 50HZ R22 User Manual

Page 2

background image

339293-YTG-C-0208

2

Unitary Products Group

Physical and Electrical Data

Model

H1RA018S78

H1RA024S78

H1RA030S78

H1RA036S78

Unit Supply Voltage

220 - 240V, 1

φ, 50Hz

Normal Voltage Range

1

1.Rated in accordance with ARI Standard 110, utilization range “A”.

207 to 253

Minimum Circuit Ampacity

9.8

14.6

20.4

20.8

Max. Overcurrent Device Amps

2

2.Dual element fuses or HACR circuit breaker.

15

25

35

35

Compressor Type

Recip

Recip

Recip

Recip

Compressor Amps

Rated Load

7.4

11.3

15.2

15.5

Locked Rotor

53

65

90

82

Crankcase Heater

No

No

No

No

Fan Motor Amps

Rated Load

.5

.5

1.8

1.8

Fan Diameter Inches

18

18

18

18

Fan Motor

Rated HP

1/12

1/12

1/4

1/4

Nominal RPM

970

970

900

900

Nominal CFM

1,650

1,650

2,350

2,350

Coil

Face Area Sq. Ft.

8.00

8.00

9.15

9.15

Rows Deep

1

1

1

1

Fin / Inches

14

14

16

16

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

3/4

Unit Charge (Lbs. - Oz.)

3

3.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

3 - 13

3 - 14

3 - 12

4 - 11

Charge Per Foot, Oz.

0.66

0.66

0.68

0.68

Operating Weight Lbs.

118

123

135

137

All dimensions are in inches. They are subject to
change without notice. Certified dimensions will be pro-
vided upon request.

Unit

Model

Dimensions

(Inches)

Refrigerant

Connection

Service Valve

Size

A

1

B

C

Liquid

Vapor

018S78

17

35

23

3/8”

3/4”

024S78

17

35

23

030S78

19

35

23

036S78

19

35

23

1.Including Fan Guard