19 supply air blower performance, 20 supply air blower performance, Johnson controls unitary products – York DY 048 User Manual
Page 18
343615-YTG-B-0308
18
Johnson Controls Unitary Products
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION
UNIT
TONNAGE
MOTOR
1
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
CF
M
WA
T
T
S
3
3
HI
1582
320
1538
335
1496
349
1458
363
1418
376
1381
390
1338
403
1298
417
1255
430
MED/HI
1488
263
1440
276
1396
290
1354
303
1309
316
1263
329
1214
343
1158
358
1085
374
MED
1339
208
1292
221
1247
234
1201
246
1152
258
1102
272
1036
288
967
303
924
313
MED/LOW 1233
171
1184
183
1135
195
1082
207
1026
220
957
235
895
248
-
-
-
-
LOW
1081
130
997
134
935
145
863
158
-
-
-
-
-
-
-
-
-
-
4
3
HI
2056
636
2017
696
1978
714
1942
734
1906
749
1864
764
1815
769
1728
743
1582
685
MED/HI
1866
539
1832
557
1795
571
1754
585
1722
602
1679
619
1636
638
1582
653
1508
639
MED
1680
408
1641
426
1594
438
1558
455
1517
472
1469
490
1415
505
1370
521
1337
536
MED/LOW 1582
362
1541
380
1495
391
1465
406
1426
423
1377
440
1326
455
1292
469
1247
485
LOW
1300
223
1258
237
1202
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
HI
2256
883
2258
931
2247
950
2223
964
2182
979
2125
971
2044
940
1958
898
1864
854
MED/HI
2145
771
2127
784
2119
808
2089
826
2051
844
2014
859
1965
861
1896
843
1801
806
MED
2020
637
1999
656
1985
675
1947
696
1910
715
1876
730
1832
740
1793
756
1725
748
MED/LOW 1757
413
1713
432
1677
451
1639
468
1597
479
1559
497
1521
513
1472
523
-
-
LOW
1570
327
1536
339
1499
356
-
-
-
-
-
-
-
-
-
-
-
-
1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Side Duct application (230 Volts)
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION
UNIT
TONNAGE
MOTOR
1
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
3
3
HI
1527
320
1485
335
1445
349
1408
363
1370
376
1334
390
1292
403
1254
417
1213
430
MED/HI
1437
263
1391
276
1349
290
1308
303
1265
316
1221
329
1174
343
1120
358
1049
374
MED
1293
208
1248
221
1205
234
1161
246
1114
258
1065
272
1002
288
935
303
894
313
MED/LOW 1191
171
1144
183
1097
195
1046
207
992
220
926
235
866
248
-
-
-
-
LOW
1045
130
964
134
904
145
-
-
-
-
-
-
-
-
-
-
-
-
4
3
HI
1985
636
1947
696
1909
714
1875
734
1840
749
1800
764
1752
769
1668
743
1528
685
MED/HI
1802
539
1768
557
1733
571
1694
585
1662
602
1621
619
1580
638
1528
653
1456
639
MED
1622
408
1585
426
1539
438
1505
455
1465
472
1419
490
1367
505
1324
521
1291
536
MED/LOW 1528
362
1489
380
1444
391
1415
406
1377
423
1330
440
1281
455
1248
469
1205
485
LOW
1256
223
1216
237
1161
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
HI
2177
883
2179
931
2169
950
2145
964
2106
979
2051
971
1973
940
1890
898
1800
854
MED/HI
2071
771
2053
784
2045
808
2016
826
1980
844
1944
859
1897
861
1830
843
1739
806
MED
1950
637
1929
656
1916
675
1880
696
1844
715
1811
730
1768
740
1731
756
1665
748
MED/LOW 1697
413
1654
432
1619
451
1583
468
1542
479
1506
497
1469
513
-
-
-
-
LOW
1516
327
1484
339
1448
356
-
-
-
-
-
-
-
-
-
-
-
-
1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Bottom Duct application (230 Volts)