Johnson Controls Unitary Products

11

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

TCGD18S41S1(H)

INDOOR COIL MODEL NO.

FC/MC/PC18

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

450

600

750

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

15.7 17.8 17.7 19.3 19.9 16.9 18.4 18.0 19.5 20.2 18.0 18.9 18.4 19.6 20.4

S.C.

16.0 13.8 12.1 12.0 9.3 17.3 15.9 13.5 13.0 9.8 18.5 17.9 14.9 13.9 10.4

KW

1.0 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9

75

T.C.

15.0 16.8 16.6 18.4 19.2 16.2 17.5 17.1 18.6 19.4 17.4 18.2 17.5 18.8 19.6

S.C.

15.3 13.6 11.7 11.6 8.9 16.6 15.6 13.2 12.8 9.6 17.9 17.6 14.7 13.9 10.3

KW

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1

85

T.C.

14.2 15.8 15.6 17.4 18.5 15.5 16.6 16.1 17.7 18.6 16.8 17.4 16.7 18.1 18.8

S.C.

14.5 13.4 11.2 11.2 8.6 15.9 15.3 12.8 12.6 9.4 17.2 17.2 14.4 13.9 10.1

KW

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2

95

T.C.

13.5 14.8 14.6 16.4 17.7 14.8 15.7 15.2 17.5 17.9 16.1 16.6 15.8 17.3 18.0

S.C.

13.8 13.1 10.8 10.7 8.2 15.2 15.0 12.5 12.4 9.1 16.6 16.9 14.2 14.0 10.0

KW

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

105

T.C.

12.6 13.7 13.2 15.1 16.5 13.8 14.6 13.8 15.5 16.7 15.0 15.5 14.4 16.0 16.8

S.C.

12.8 12.5 10.2 10.3 7.9 14.1 14.1 11.8 11.9 8.8 15.4 15.7 13.4 13.6 9.8

KW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

115

T.C.

11.6 12.6 11.8 13.8 15.4 12.7 13.5 12.5 14.2 15.5 13.8 14.5 13.1 14.6 15.6

S.C.

11.9 11.9 9.6 9.8 7.6 13.1 13.2 11.2 11.6 8.6 14.3 14.6 12.7 13.3 9.6

KW

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

125

T.C.

10.7 11.4 10.5 12.5 14.2 11.7 12.4 11.2 12.9 14.3 12.7 13.4 11.8 13.3 14.4

S.C.

11.0 11.2 9.0 9.4 7.3 12.1 12.3 10.5 11.2 8.3 13.1 13.5 12.0 12.9 9.4

KW

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

HC18

1.00 1.00 1.00

UC18

1.00 1.00 1.00

AHP18

1.00 1.00 1.00

MV12B

FC/MC18B

1.02 1.03 0.89

MA08B

FC/MC18B

1.00 1.00 1.00

F4FP024

1.00 1.00 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC18A 1.02

1.03

0.89

PV9*A12

FC/MC/PC18A 1.01

1.03

0.88

P(C,V)9*B12

FC/MC/PC18B 1.02

1.03

0.89

PV8*A12

HC18 1.02

1.03

0.89

PV9*A12

HC18 1.01

1.03