York YP9C*C User Manual
Page 3
538513- YTG-A-0809
Johnson Controls Unitary Products
3
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Perfor-
mance” table represents blower performance WITHOUT filters.
All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.
NOTE: Single side return above 1800 CFM is approved as long
as the filter velocity does not exceed filter manufacturer’s rec-
ommendation and a transition is used to allow use of a 20 x 25
filter.
NOTES:
1. Air velocity through throwaway type filters may not exceed 300 feet per min-
ute (91.4 m/min). All velocities over this require the use of high velocity fil-
ters.
2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For
CFM greater than 1800, you may use two side returns or one side and the
bottom or one return with a transition to allow use of a 20x25 filter.
All furnaces approved for alcove and attic installation.
ACCESSORIES
Propane (LP) Conversion Kit -
1NP0681 - All Models
This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation.
Do not use Conversion Kit S1-1NP0680 with these models, as
the control/gas valve combination have been updated, and that
kit S1-1NP0680 will not function correctly with these models.
Concentric Vent Termination -
S1-1CT0302 (2")
S1-1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Elimi-
nates unslightly elbows for a cleaner installation.
Sidewall Vent Termination Kit -
S1-1HT0901 (3")
S1-1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a more
attractive termination for locations where the terminal is visable
on the side of the home.
Condensate Neutralizer Kit -
1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for installa-
tion in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
Side Return Filter Racks -
1SR0200 - All Models
1SR0402 - All Models
1SF0101 - All Models
Bottom Return Filter Racks -
1BR0517 or 1BR0617 - For 17-1/2” cabinets
1BR0521 or 1BR0621 - For 21” cabinets
1BR0524 or 1BR0624 - For 24-1/2” cabinets
1BR05xx series are galvanized steel filter racks. 1BR06xx are
pre-painted steel filter racks to match the appearance of the fur-
nace cabinet.
Combustible Floor Base Kit -
For installation of these furnaces in downflow applications
directly onto combustible flooring material, These kits are
required to prevent potential overheating situations. These kits
are also required in any applications where the furnace in
installed in a downflow configuration without an evaporator coil,
where the combustible floor base kit provides access for com-
bustible airflow.
1CB0517 - For 17-1/2” cabinets
1CB0521 - For 21” cabinets
1CB0524 - For 24-1/2” cabinets
EAC Transition Kits -
For installation of EAC accessories with these furnaces to pro-
vide easy transition of return airflow through the EAC to get the
proper sealing and reduced airflow leakage.
1TK1001 - For all models using side return
1TK1017 - For 17-1/2” cabinets using bottom return
1TK1021 - For 21” cabinets using bottom return
1TK1024 - For 24-1/2” cabinets using bottom return
High Altitude - No high altitude kits are required.
Thermostats - Compatible thermostat controls are available
through accessory sourcing. For optimum performance and
installation, refer to the UPGNET “Low Voltage Wiring Diagram”
document to select and apply controls.
Recommended Filter Sizes
CFM
Cabinet
Size
Side
(in)
Bottom
(in)
1200
B
16 x 25
16 x 25
1600
C
16 x 25
20 x 25
2000
C
(2) 16 x 25
20 x 25
2000
D
(2) 16 x 25
22 x 25
Unit Clearances to Combustibles
Application
Upflow
Downflow
Horizontal
Top
1" 0" 0"
Vent
0" 0" 0"
Rear
0" 0" 0"
Side
0" 0" 1"
Front
1
1. Line contact only permitted between lines formed by the intersection of the
rear panel and side panel (top in horizontal position) of the furnace jacket
and building joists, studs or framing.
0" 0" 0"
Floor
Combustible
Combustible
2
2. For combustible floors only when used with special sub-base.
Combustible
Closet
Yes
Yes
Yes
Line Contact
No
No
Yes