20 dj electrical data with powered, Convenience outlet – York DJ 180 User Manual
Page 26
261660-YTG-C-0707
26
Unitary Products Group
NOTE 1: HACR Type per NEC.
TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
180
(15)
208
22.4
164
2.1
15.4
10.0
None
0.0
~
~
84.2
100
E18
13.5
1
37.5
84.2
100
E36
27.0
2
75.1
125.4
150
E54
40.6
2
112.6
172.6
175
E72
54.1
2
150.1
181.9
200
230
22.4
164
2.1
15.4
10.0
None
0.0
~
~
83.2
100
E18
18.0
1
43.3
84.6
100
E36
36.0
2
86.6
138.8
150
E54
54.0
2
129.9
160.4
175
E72
72.0
2
173.2
203.7
225
460
10.9
100
1.1
7.2
5.0
None
0.0
~
~
41.1
50
E18
18.0
1
21.7
42.3
50
E36
36.0
2
43.3
69.4
70
E54
54.0
2
65.0
80.2
90
E72
72.0
2
86.6
101.9
110
575
8.3
78
0.9
5.9
4.0
None
0.0
~
~
32.2
40
E18
18.0
1
17.3
34.0
40
E36
36.0
2
34.6
55.7
60
E54
54.0
2
52.0
64.3
70
E72
72.0
2
69.3
81.7
90
210
(17 1/2)
208
25.6
190
2.1
20.0
10.0
None
0.0
~
~
96.0
110
E18
13.5
1
37.5
96.0
110
E36
27.0
2
75.1
131.2
150
E54
40.6
2
112.6
178.4
200
E72
54.1
2
150.1
187.7
200
230
25.6
190
2.1
20.0
10.0
None
0.0
~
~
96.0
110
E18
18.0
1
43.3
96.0
110
E36
36.0
2
86.6
145.8
150
E54
54.0
2
129.9
167.4
175
E72
72.0
2
173.2
210.7
225
460
12.8
95
1.1
10.0
5.0
None
0.0
~
~
48.2
60
E18
18.0
1
21.7
48.2
60
E36
36.0
2
43.3
72.9
80
E54
54.0
2
65.0
83.7
90
E72
72.0
2
86.6
105.4
110
575
10.3
75
0.9
8.2
4.0
None
0.0
~
~
39.0
45
E18
18.0
1
17.3
39.0
45
E36
36.0
2
34.6
58.6
60
E54
54.0
2
52.0
67.2
70
E72
72.0
2
69.3
84.5
90