Physical and electrical data – York E4TS030 THRU 060 User Manual
Page 3
036-21342-002 Rev. E (0505)
Unitary Products Group
3
Physical and Electrical Data
MODEL
E4TS030
E4TS036
E4TS048
E4TS060
UNIT SUPPLY VOLTAGE
208/230-1-60
NORMAL VOLTAGE RANGE
1
1. Rated in accordance with ARI Standard 110, utilizaton range “A”.
187 to 252
MIN. CIRCUIT AMPACITY
14.8
18.3
28.0
34.4
MAX. OVERCURRENT DEVICE AMPS
2
2. Dual element fuses or HACR circuit breaker.
25
30
50
60
COMPRESSOR TYPE
T27B264CBCA
T27B355CBCA
T29A464BBCA
T29A544BBCA
COMPRESSOR AMPS
RATED LOAD
11.3
14.1
21.2
26.3
LOCKED ROTOR
65
84
130
142
CRANKCASE HEATER
YES
YES
YES
YES
FAN MOTOR AMPS
RATED LOAD
.7
.7
1.5
1.5
FAN DIAMETER INCHES
24
24
24
24
FAN MOTOR
RATED HP
1/10
1/10
1/4
1/4
NOMINAL RPM
825
825
825
850
NOMINAL CFM
2650
2650
3200
3200
COIL
FACE AREA SQ. FT.
20.0
20.0
20.0
20.0
ROWS DEEP
1
1
2
2
FIN / INCH
16
16
13
13
LIQUID LINE OD
3/8
3/8
3/8
3/8
VAPOR LINE OD
7/8
7/8
7/8
7/8
UNIT CHARGE, (LBS - OZ)
3
3. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.
9 - 9
10 - 1
12 - 1
13 - 1
CHARGE PER FOOT, OZ
.70
.70
.70
.70
OPERATING WEIGHT LBS.
242
242
310
310
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES
UNIT
MODEL
E4TS
DIMENSIONS
REFRIGERANT
CONNECTION
LINE SIZE
A
B
C
LIQUID VAPOR
030
31-7/8
35
35
3/8
7/8
036
31-7/8
35
35
048
31-7/8
35
35
060
37-7/8
35
35