York YMA024 User Manual
Page 14
036-21570-002 Rev. D (0605)
14
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YMA04211
INDOOR COIL MODEL NO.
G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1200
1400
1600
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
40.0 43.8 42.6 47.1 46.4 42.0 45.2 43.7 47.9 46.0 44.0 46.6 44.8 48.7 45.5
S.C.
42.3 38.6 32.9 32.6 23.9 44.2 42.0 35.4 34.5 24.4 46.2 45.4 37.9 36.4 24.9
K.W.
2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
75
T.C.
38.6 41.7 40.7 45.2 45.4 40.7 43.1 41.6 45.9 45.3 42.8 44.5 42.6 46.7 45.2
S.C.
40.7 37.9 31.9 31.8 23.4 42.6 41.0 34.4 33.9 24.2 44.5 44.2 36.9 36.0 25.0
K.W.
3.1 3.1 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2 3.2 3.2 3.2 3.2 3.2
85
T.C.
37.1 39.6 38.7 43.3 44.3 39.3 41.0 39.6 44.0 44.6 41.5 42.4 40.5 44.7 44.8
S.C.
39.2 37.1 31.0 31.0 23.0 41.1 40.1 33.5 33.2 24.0 42.9 43.0 35.9 35.5 25.1
K.W.
3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.6 3.6
95
T.C.
35.6 37.5 36.8 41.3 43.3 38.0 38.9 37.6 42.0 43.9 40.3 40.2 38.3 42.7 44.5
S.C.
37.6 36.3 30.1 30.2 22.5 39.5 39.1 32.5 32.6 23.9 41.3 41.8 35.0 35.0 25.2
K.W.
3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 4.0 4.0
105
T.C.
33.7 35.1 34.3 38.5 40.3 35.8 36.5 35.0 39.1 40.8 37.9 37.8 35.7 39.7 41.4
S.C.
35.6 34.7 29.0 29.0 21.5 37.2 37.0 31.3 31.2 22.9 38.9 39.3 33.6 33.4 24.3
K.W.
4.4 4.4 4.4 4.5 4.5 4.4 4.4 4.4 4.5 4.5 4.5 4.5 4.4 4.5 4.5
115
T.C.
31.8 32.9 31.8 35.7 37.3 33.7 34.2 32.5 36.3 37.8 35.6 35.4 33.1 36.9 38.3
S.C.
33.6 33.1 27.9 27.7 20.5 35.1 35.0 30.0 29.8 22.0 36.6 36.8 32.2 31.9 23.4
K.W.
4.9 4.9 4.9 5.0 5.0 5.0 5.0 4.9 5.0 5.0 5.0 5.0 4.9 5.0 5.1
125
T.C.
30.0 30.6 29.4 33.0 34.3 31.6 31.8 29.9 33.5 34.8 33.2 33.1 30.5 34.0 35.3
S.C.
31.6 31.5 26.8 26.5 19.5 32.9 32.9 28.8 28.4 21.0 34.3 34.4 30.8 30.3 22.5
K.W.
5.5 5.5 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.5 5.5 5.5 5.5 5.6
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2FP048
0.99 0.98 1.00
N1VSC16
G2FD048(S,H)21(T)
1.01 0.99 0.94
N1VSD20
G2FD048(S,H)24(T)
1.01 0.98 0.95
N1AHC16
G2FD048(S,H)21(T)
1.00 1.01 1.00
N1AHD20
G2FD048(S,H)24(T)
1.00 1.01 1.00
G1FA048S21
1.00 1.00 1.00
G2FD048(S,H)21,24
1.00 1.01 1.00
G1NA060S24T
1.01 1.01 0.99
G1HD048
0.99 0.99 0.99
G1HA048H21
0.99 0.97 0.99
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P*DUC20V
G1FA048S21
1.00 1.01 0.96
P*DUC20V
G2FD048(S,H)21(T) 1.01 1.02 0.96
P1XUC16V
G1FA048S21
1.00 1.01 0.96
P1XUC16V
G2FD048(S,H)21(T) 1.01 1.02 0.96
P1XUC20V
G1FA048S21
1.00 1.01 0.96
P1XUC20V
G2FD048(S,H)21(T) 1.01 1.02 0.96
P1XDD20V
G2FD048(S,H)24(T) 1.01 1.02 0.98
P1XDC20V
G2FD048(S,H)21(T) 1.01 1.02 1.00
P1XDC20V
G1HA048H21
0.99 0.97 0.98
P1XDD20V
G2FD048(S,H)24(T) 1.01 1.02 0.98