Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

YMA03011

INDOOR COIL MODEL NO.

G2FD030S17

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

800

1000

1200

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

57

62

62

67

72

57

65

T.C.

29.1 32.6 32.6 35.6 35.2 31.4 33.1 35.3 35.0 34.4 33.7 33.7 38.0 34.4 33.7

S.C.

29.2 26.8 22.6 22.4 17.0 31.5 28.7 26.4 21.8 17.4 33.8 30.6 30.2 21.2 17.8

K.W.

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

75

T.C.

27.6 30.4 30.2 33.5 34.6 29.7 31.3 32.3 33.3 34.2 31.9 32.2 34.4 33.2 33.7

S.C.

27.7 25.8 21.8 21.7 17.0 29.8 28.0 25.1 22.2 17.7 32.0 30.2 28.3 22.7 18.4

K.W.

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

85

T.C.

26.0 28.2 27.8 31.4 34.0 28.1 29.5 29.3 31.7 33.9 30.1 30.7 30.7 31.9 33.8

S.C.

26.1 24.8 21.0 21.0 16.9 28.2 27.3 23.7 22.6 18.0 30.2 29.8 26.5 24.2 19.1

K.W.

2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6

95

T.C.

24.5 26.0 25.4 29.3 33.4 26.4 27.7 26.2 30.0 33.7 28.3 29.3 27.1 30.7 33.9

S.C.

24.6 23.8 20.1 20.3 16.9 26.5 26.6 22.4 23.0 18.3 28.4 29.5 24.7 25.7 19.7

K.W.

2.6 2.6 2.6 2.7 2.7 2.6 2.6 2.6 2.7 2.8 2.7 2.7 2.7 2.7 2.8

105

T.C.

23.0 24.1 23.4 26.8 30.5 24.6 25.5 24.4 27.4 30.8 26.3 27.0 25.4 28.0 31.0

S.C.

23.0 22.7 19.1 19.5 15.9 24.6 24.9 21.5 22.0 17.3 26.3 27.1 23.9 24.5 18.7

K.W.

2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 3.0 2.9 2.9 2.8 2.9 3.0

115

T.C.

21.5 22.3 21.4 24.4 27.7 22.9 23.5 22.6 24.8 27.9 24.3 24.7 23.8 25.3 28.2

S.C.

21.6 21.6 18.1 18.7 14.9 22.9 23.2 20.6 21.0 16.3 24.4 24.8 23.1 23.4 17.7

K.W.

3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1 3.2 3.1 3.1 3.0 3.1 3.2

125

T.C.

20.0 20.4 19.5 22.0 24.8 21.2 21.4 20.9 22.3 25.1 22.3 22.5 22.2 22.6 25.4

S.C.

20.1 20.5 17.2 17.9 13.9 21.1 21.5 19.8 20.1 15.3 22.4 22.6 22.3 22.3 16.7

K.W.

3.2 3.2 3.1 3.2 3.3 3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.2 3.3 3.4

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

F2RC/F2FC036

0.99 0.97 0.99

F2RP/F2FP/F3FP030

0.99 0.97 0.99

N1VSB12

G2FD030(S,H)17(T)

1.01 0.99 0.94

N1AHB08

G2FD030(S,H)17(T)

1.00 1.00 1.00

N1AHB12

G2FD030(S,H)17(T)

1.00 1.00 1.00

G1FA036S14

1.01 1.00 1.00

G1FA036S17,21

1.00 1.00 1.00

G2FD030(S,H)17(T)

1.00 1.00 1.00

G2FD035(S,H)14(T)

1.00 1.00 1.00

G1NA036S17J

1.01 1.00 1.00

G1NA036S21C

1.01 1.00 1.00

G1HD036

1.02 1.02 1.00

G1HA036H14

1.03 1.00 1.00

G1HA036H17

1.03 1.01 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

P*DUA12V

G1FA036S14

1.01 0.99 0.94

P*DUB16V

G1FA036S17

1.02 1.03 0.94

P*DUB16V

G2FD030(S,H)17(T)

1.02 1.03 0.94

P*DUC20V

G1FA036S21

1.01 1.01 0.93

P1XUB12V

G1FA036S17

1.01 1.02 0.95

P1XUB12V

G2FD030(S,H)17(T)

1.01 1.02 0.95

P1XUC16V

G1FA036S21

1.01 1.01 0.93

P1XUC20V

G1FA036S21

1.01 1.00 0.93

P1XDB12V

G2FD030(S,H)17(T)

1.01 1.01 0.95

P1XDB12V

G1HA036H17

1.01 1.02 0.95