York SUNLINE 2000 D2CG 072 User Manual

Page 8

background image

NOTE: Install filters so that “Air Flow” arrows point toward the

unit.

8. Install filter cover over the end of the hood with one screw

(center of hood), securing filters into position.

CAUTION: When proceeding with Steps 9 and 10, extreme

care must be exercised while turning both the set
point and minimum position adjusting screws to
prevent twisting them off.

9. The enthalpy set point for the dampers may now be set by

selecting the desired set point from graph in Figure 7. For
a single enthalpy economizer, carefully turn the set point

adjusting screw to the “A”, “B”, “C” or “D” setting corre-
sponding to the lettered curve. For a dual enthalpy econo-
mizer, carefully turn the set point adjusting screw fully
clockwise past the “D” setting.

10. To check that the damper blades move smoothly without

binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals “R” to “G”. With terminals “R” to “G” energized,
turn the minimum position screw counterclockwise until the
desired minimum position has been attained.

11. Replace the filter section access panel.

FIG. 7 - ENTHALPY SET POINT ADJUSTMENT

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

Economizer

1, 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

Bottom Duct Connections

1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

1

Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2

The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM

TABLE 4 - STATIC RESISTANCES

530.18-N8Y