1. At higher evaporator airflows, and wet bulb conditions condensate carry-over may occur. Adjust airflow downward as necessary.

2. Values include pressure drop from wet coil and clean filters.

3. Shaded areas indicate oversize motors.

TABLE 3: SUPPLY AIR BLOWER PERFORMANCE CH060-120, 5 TO 10 TON HORIZONTAL MODELS

MODEL #

SUPPLY CFM

EXTERNAL STATIC PRESSURE - Inches W.C.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

RPM BHP

CH060

1800

846

0.41

936

0.48 1024 0.56 1107 0.64 1195 0.74 1259 0.82 1325 0.90 1400 0.99

-

-

2000

917

0.54

999

0.62 1079 0.71 1157 0.79 1233 0.89 1305 0.98

-

-

-

-

-

-

2200

994

0.70 1069 0.79 1142 0.88 1214 0.98

-

-

-

-

-

-

-

-

-

-

CH096

3000

810

0.65

900

0.78

986

0.91 1066 1.04 1143 1.17 1221 1.32 1294 1.48 1363 1.63

1433

1.79

3200

851

0.78

938

0.91 1018 1.04 1095 1.18 1170 1.32 1236 1.42 1305 1.56 1380 1.74

1447

1.90

3400

892

0.91

974

1.05 1051 1.19 1125 1.33 1196 1.48 1266 1.64 1320 1.81 1390 1.90

-

-

CH120

3600

927

1.05 1006 1.20 1081 1.34 1152 1.50 1220 1.65 1287 1.81 1353 1.98 1405 2.07

1472

2.17

4000

1012 1.40 1085 1.56 1153 1.73 1220 1.89 1283 2.06 1345 2.23 1405 2.41 1464 2.59

1522

2.78

4400

1100 1.83 1166 2.00 1230 2.18 1292 2.37 1351 2.55 1410 2.74 1466 2.92

-

-

-

-