On/off switch, Warning: shock hazard – Xantrex Technology PV225S-480-P User Manual
Page 28
![background image](/manuals/226175/28/background.png)
Introduction
1–8
152606
On/Off Switch
The PV225S
incorporates a maintained position O
N
/O
FF
switch (S3) located on
the front door of the main enclosure. Under normal conditions, the O
N
/O
FF
switch
is in the O
N
position. Turning the switch to the
OFF
position will initiate an
immediate controlled shutdown of the PV225S
and opens both the main AC and
DC contactors within the unit. The main AC and DC contactors cannot be closed
unless the switch is in the
ON
position. The PV225S
is prevented from being
restarted until the O
N
/O
FF
switch is turned back to the O
N
position.
WARNING: Shock Hazard
Disengaging the main enclosure door interlock switch does NOT remove all hazardous
voltages from inside the inverter. Before attempting to service the PV225S, follow the
de-energize Lockout and Tag procedure on page x.
WARNING: Shock Hazard
Turning the O
N
/O
FF
switch to the O
FF
position does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV225S, follow the de-energize
Lockout and Tag procedure on page x.
Figure 1-3 On/Off Switch (S3)
O
N
/O
FF
Switch
(S3)