Watlow Electric RUI/Gateway User Manual
Page 20
RUI/Gateway & Modbus
®
TCP
Configuration & Programming Example
Using KEPServerEX 4.0
Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2008 Watlow Electric Mfg Co 20
FM 4/08
42. Lastly, in the screen shot below, notice that the 12
th
pointer has indeed been changed to Idle
Set Point (circle) and the tag created to reflect this (arrow) shows the current Idle Set Point for
PM1. Compare this to the default assembly found in step 37 above.