Rui/gateway & modbus – Watlow Electric RUI/Gateway User Manual
Page 2
RUI/Gateway & Modbus
®
TCP
Configuration & Programming Example
Using KEPServerEX 4.0
Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2008 Watlow Electric Mfg Co 2
FM 4/08
3.
Some notables regarding the graphic above. In the steps that follow we are going to focus on
four of the prompts shown: a. Modbus
®
Enable (
Mb;E) b. Gateway instance (GTW)
c.
Gateway
enable (
du;En) d. Modbus
®
offset (
M;oF)
4.
Notice in the graphic in step 2 that the RUI/Gateway has 2 “Com” instances. Com instance 1
will always be Standard Bus and Com instance 2 will always be the user protocol of choice, in
this case, Modbus
®
TCP. This protocol when ordered also comes standard with EtherNet/IP
TM
(Industrial Protocol) as well. When setting the prompts for Com instance 2 you must first
enable Modbus
®
TCP, EtherNet/IP
TM
or both. For the purpose of this paper the prompt
displayed as
Mb;E will be set to yes (Modbus
®
TCP enabled). If a step-by-step example is
needed to fully configure the RUI/Gateway refer to step one and download the appropriate
user manual.
5.
To implement the network shown in step two the following settings will need to be entered:
Further explanation of these prompts and their associated enumerated values will follow.
6.
After completing the configuration as shown above as well as your Com 1 settings for the
Standard Bus side this will complete the RUI/Gateway configuration.
7.
Note that KEPServerEX is one of many software packages on the market today that include
the Modbus
®
TCP driver; this procedure is for KEPServerEX.
8.
The following screen shots capture a step-by-step procedure to successfully establish
Communications between the computer (PC) running KEPServerEX and the EZ-ZONE
®
RUI/Gateway (Com instance 2) over Modbus
®
TCP. Once communications are established
over Com instance 2 we will then look further at the KEPServerEX configuration that will
enable communications through the RUI/Gateway to Com instance 1 and the EZ-ZONE
®
PM
controls (1 - 4) over Standard Bus; thereby establishing a live and active communications link
between dissimilar networks.
Gateway
Instance
Enable
Gateway
Instance
Modbus
®
Offset
GTW = 1 Du;En = Yes M;oF = 0
GTW = 2 Du;En = Yes M;oF = 5000
GTW = 3 Du;En = Yes M;oF = * 10000
GTW = 4 Du;En = Yes M;oF = * 15000
* The RUI allows for a maximum entry of 9999 due to the limitations of the 7 segment display. To enter
an offset > 9999 EZ-ZONE
®
configurator software must be used.