beautypg.com

Rui/gateway & modbus – Watlow Electric RUI/Gateway User Manual

Page 2

background image

RUI/Gateway & Modbus

®

TCP

Configuration & Programming Example

Using KEPServerEX 4.0

Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2008 Watlow Electric Mfg Co 2

FM 4/08

3.

Some notables regarding the graphic above. In the steps that follow we are going to focus on
four of the prompts shown: a. Modbus

®

Enable (

Mb;E) b. Gateway instance (GTW)

c.

Gateway

enable (

du;En) d. Modbus

®

offset (

M;oF)


4.

Notice in the graphic in step 2 that the RUI/Gateway has 2 “Com” instances. Com instance 1

will always be Standard Bus and Com instance 2 will always be the user protocol of choice, in
this case, Modbus

®

TCP. This protocol when ordered also comes standard with EtherNet/IP

TM

(Industrial Protocol) as well. When setting the prompts for Com instance 2 you must first
enable Modbus

®

TCP, EtherNet/IP

TM

or both. For the purpose of this paper the prompt

displayed as

Mb;E will be set to yes (Modbus

®

TCP enabled). If a step-by-step example is

needed to fully configure the RUI/Gateway refer to step one and download the appropriate
user manual.


5.

To implement the network shown in step two the following settings will need to be entered:






Further explanation of these prompts and their associated enumerated values will follow.



6.

After completing the configuration as shown above as well as your Com 1 settings for the

Standard Bus side this will complete the RUI/Gateway configuration.

7.

Note that KEPServerEX is one of many software packages on the market today that include
the Modbus

®

TCP driver; this procedure is for KEPServerEX.

8.

The following screen shots capture a step-by-step procedure to successfully establish

Communications between the computer (PC) running KEPServerEX and the EZ-ZONE

®

RUI/Gateway (Com instance 2) over Modbus

®

TCP. Once communications are established

over Com instance 2 we will then look further at the KEPServerEX configuration that will

enable communications through the RUI/Gateway to Com instance 1 and the EZ-ZONE

®

PM

controls (1 - 4) over Standard Bus; thereby establishing a live and active communications link
between dissimilar networks.

Gateway

Instance

Enable

Gateway

Instance

Modbus

®

Offset

GTW = 1 Du;En = Yes M;oF = 0
GTW = 2 Du;En = Yes M;oF = 5000
GTW = 3 Du;En = Yes M;oF = * 10000
GTW = 4 Du;En = Yes M;oF = * 15000

* The RUI allows for a maximum entry of 9999 due to the limitations of the 7 segment display. To enter

an offset > 9999 EZ-ZONE

®

configurator software must be used.