Operating instructions – Weil-McLain CGi User Manual
Page 20

CGa, CGi, CGs, EG, EGH, LGB, PEG, PFG Boilers
20
Part Number 550-110-592/1000
FOR YOUR SAFETY READ BEFORE LIGHTING
OPERATING INSTRUCTIONS
TO TURN OFF GAS TO THE APPLIANCE
•
Do not try to light any appliance.
•
Do not touch any electric switch; do not use any phone
in your building.
•
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
If you cannot reach your gas supplier, call the fire
department.
WHAT TO DO IF YOU SMELL GAS
If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury or loss of life.
1.
Stop!
Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with
Effikal
vent damper
Model RVGP,
place service switch in
Hold
Damper Open
position.
4. Turn off all electrical power to the appliance.
5. When equipped with
Johnson Controls
vent damper
Model M35,
manually rotate
damper blade in direction of arrow to
Open
position indicated on damper assembly.
6. Turn gas control knob clockwise
to
OFF
.
7. When equipped with vent damper, verify damper blade is in full open position.
8. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If
you smell gas,
STOP!
Follow
"B"
in the safety information above. If you don't smell
gas, go to the next step.
9. Turn gas control knob counterclockwise
to
PILOT
.
10. Turn on all electric power to the appliance.
11. When equipped with
Effikal
vent damper, place service switch in
Automatic Operation
position.
12. Set thermostat to desired setting.
13. If the appliance will not operate, follow the instructions "
TO TURN OFF GAS TO
APPLIANCE
" below and call your service technician or gas supplier.
14. Replace front panel.
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove front panel.
4. Turn gas control knob clockwise
to OFF.
5. Replace front panel.
Operating instructions
•
Spark-ignited pilot
•
Gas valve — Robertshaw 7000DERHC
A. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do
not
try to light the pilot by hand.
B. Before
OPERATING
, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air and
will settle on the floor. See below.
C. Use only your hand to turn the gas control knob. Never use tools. If
the selector arm will not depress or move by hand, don't try to repair
it, call a qualified service technician. Force or attempted repair may
result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
EGH-85 to EGH-125,
PFG-6 to PFG-8
Position
indicator
Gas control knob
(shown in
position)
ON
59205b