Series f4p, Microdin, Power series – Watlow EM Gateway User Manual
Page 19
19
Series F4P
Operation Mode – register 200 with choice of Auto or Manual as read only
Input 1 Error – register 101 with choice of Sensor Error or Ok as read only
Input 2 Error – register 105 with choice of Sensor Error or Ok as read only
Input 3 Error – register 109 with choice of Sensor Error or Ok as read only
Process Value Input 1 – register 100 as read only
Process Value Input 2 – register 104 as read only
Process Value Input 3 – register 108 as read only
Auto Set Point – register 300 as read/write
Alarm Status Output 2 – register 102 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched,
Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm
Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only
Alarm Status Output 3 – register 106 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched,
Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm
Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only
Alarm 1 Acknowledge – register 312 with choice to clear alarm as write only
Alarm 2 Acknowledge – register 331 with choice to clear alarm as write only
Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still
exists.
MicroDIN
Operation Mode – register 200 with choice of Auto or Manual as read only
Input Error – register 101 with choice of Sensor Error or Ok as read only
Process Value Input 1 – register 100 as read only
Auto Set Point – register 300 as read/write
Alarm Status Output 2 – register 106 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched,
Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm
Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only
Alarm Acknowledge – register 331 with choice to clear alarm as write only
Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still
exists.
Power Series
Heat Sink Temperature in Degrees C - register 1590 as read only
Load Current in Amps RMS on Line 1 - register 154 as read only (Based on configuration)
Load Current in Amps RMS on Line 2 - register 164 as read only (Based on configuration)
Load Current in Amps RMS on Line 3 - register 174 as read only (Based on configuration)
Note: Display of current on lines 1, 2, and 3 depends on the number of zones, the installed options and
the load type.